Products

Search by features


ПвБШвнг(А)-LS – (PvBShvng(A)-LS)

ПвБШвнг(А)-LS – (PvBShvng(A)-LS)
Price on request
₽0
By category
Force cables
Voltage
6000
In execution
Flame retardant (-ng(А)) / With low smoke and gas emission (-LS)
Insulation
Copper
Number and nom, cross-section of CCC and screens, nxmm2, external diameter, mm, weight of 1km of cable, kg
PvBShvng(A)-LS
Number and nominal cross-section of conductors (mm2) External diameter of cable, mm Weight, kg
3х35/16 41,76 3206
3х50/16 44,82 3856
3х70/16 43,54 4310
3х95/16 46,27 5199
3х120/16 48,64 6050
3х150/25 51,61 7187
3х185/25 54,41 8348
3х240/25 58,64 10193

₽0 for 1 м

Quantity
- + м Add to cart

SCOPE AND PURPOSE

The cables are designed for transmission and distribution of electric energy in stationary electric installations, for installation in cable structures, buildings and underground structures, including flammable and explosive areas.

The class of fire hazard of the cables according to GOST 31565-2012 П1б.8.2.2.2.

 

TECHNICAL DATA

Nominal voltage, kV: 6

Ambient temperature during cable operation, °С: - from -50 to +50

Resistant with a relative humidity up to 98% at ambient temperature, degree Celsius, up to: +35

Minimum bending radius, diameters of cable: 12

Service life, years, not less: 30

Smoke generation in the test cell: not more than 50%

Flame retardant at group installation on category: А

Equivalent toxicity index, g/m3 , more than: 40

 

STRUCTURE

Conductor

Copper, multi-wire of the 1st or 2nd classes according to GOST 22483-2012, of cross section from 35 to 240 mm2

Insulation

Cross-linked, halogen free, polymer composition.

Core arrangement.

Insulated conductors are twisted in a cable core.

The cables have got distinctive markings of insulated cores.

Inner sheath

It is made by extrusion with filling with the halogen free polymer compositions.

Screen

It is made by taping with the tape of conductive nonwoven fabric or copper tapes and copper wires and copper tapes.

Separating layer

Taping with a tape of nonwoven fabric.

Bedding

For cables of types PvBShvng(A)-LS the bedding is made of halogen free polymer composition.

Cable armoring

It is laid helically with two steel, galvanized tapes.

It is possible to lay the PET-tapes by winding or longitudinally over the armor.

Cable sheath or jacket

PVC-compound of low fire hazard.

By category
Force cables
Voltage
6000
In execution
Flame retardant (-ng(А)) / With low smoke and gas emission (-LS)
Insulation
Copper
Number and nom, cross-section of CCC and screens, nxmm2, external diameter, mm, weight of 1km of cable, kg
PvBShvng(A)-LS
Number and nominal cross-section of conductors (mm2) External diameter of cable, mm Weight, kg
3х35/16 41,76 3206
3х50/16 44,82 3856
3х70/16 43,54 4310
3х95/16 46,27 5199
3х120/16 48,64 6050
3х150/25 51,61 7187
3х185/25 54,41 8348
3х240/25 58,64 10193