KVVGng(A)-LS, KVVGzng(A)-LS, KVVGЕng(A)-LS, KVBbShvng(A)-LS, KVVG-Png(A)-LS, according to specifications 3563-010-53972660-2010
specifications 3563-010-53972660-2010

Conductor

Copper, single-wire, of the 1 class according to GOST 22483, with the cross-section from 0.75 to 6 mm2.

Insulation

PVC-compound of low flammability.

Core arrangement and twisting

From 4 to 127 insulated conductors.

The insulated conductors are twisted; there is a marker pair in each layer. It is allowed digital and color coded marking of the conductors.

KVVG-Png(A)-LS is manufactured in 4-core modification only, conductors must be laid in parallel in one flat.

Separating layer

PVC-compound of low flammability.

Screen

For cables of types KVVGЕng(A)-LS is made in the form of taping with aluminum polyethylene tape.

Cable armoring

For cables of types KVBbShvng(A)-LS is laid helically with two steel, galvanized tapes.

Over sheath

PVC-compound of low fire hazard.

The cables are designed for fixed connection to electrical devices and equipment, to assemblies of clamps of electrical switch gear with the nominal alternating voltage 660V of frequency 100 Hz or direct voltage up to 1000V, for group installation with taking into account the volume of combustible load of the cables, in cable structures and premises of indoor electric units including residential and public buildings.

The screened cables are used when it is necessary to protect the electrical circuits from the influence of external electric fields.

The armored cables are used in case of danger of mechanic damage in process of operation, if the cables are not exposed to significant tensile force.

The climate modification УХЛ and T, categories of location 1 and 5 according to GOST 15150.

The class of fire hazard of the cables according to GOST 31565 П1б.8.2.2.2.

Nominal voltage, kV 0.66
Ambient temperature during cable operation, °С from – 50 to + 50
Minimum bending radius of the cables, diameters of the cable for armored 10
for non-armored 6
The ambient temperature for installation of the cables (without preheat), °С, not below - 15
Smoke generation in the test cell not more than 50%