RVGng(A)-FRLS, RVG-Рng(A)-FRLS, RVGЕng(A)-FRLS, according to specifications 16.K121-026-2013
specifications 16.K121-026-2013

Number of conductors

For RVGng(A)-FRLS and RVGЕng(A)-FRLS from 1 to 5.

For RVG-Рng(A)-FRLS 2 or 3.

Conductor

Copper, of circular form, single-wire core, with the cross-section from 1.5 to 16mm2 or multiwire core with the cross-section from 10 to 16mm2

Insulation

Ceramics-forming rubber.

Core arrangement and twisting

For RVGng(A)-FRLS and RVGЕng(A)-FRLS insulated conductors from 2 to 5 core cables twisted in a cable core.

For RVG-Рng(A)-FRLS insulated cores situated in parallel in one flat.

Inner sheath

For RVGng(A)-FRLS and RVGЕng(A)-FRLS PVC-compound of low fire hazard.

Screen

For cables of types RVGЕng(A)-FRLS - copper tape.

Over sheath

PVC-compound of low fire hazard.

The cables are designed for transmission and distribution of electric power in stationary installations on the nominal alternating voltage to 0.66 and 1kV and frequency 50 Hz.

The cables do not spread combustion at group stationary installation of cable lines, in the absence of mechanical effects and keep working when exposed to flame not less than 180 minutes.

They are designed for wiring and networks of the wiring circuits of emergency power supply of the equipment (current collectors), in residential and public buildings, in the surgical departments of hospitals, in office premises, equipped with computer and microprocessor devices, entertainment complexes and sports facilities, as well as at other objects with the high demand of fire safety.

The cables of types RVG-Png(A)-FRLS are used for laying under plaster, where a seal is not required when entering.

The class of fire hazard of the cables according to GOST 31565 for cables П1б.1.2.2.2.

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, °С from – 40 to + 50
Minimum bending radius, diameters of cable for multi-wire 7,5
for single-wire 10
The cables are laid at temperature (without preheat), °С, not below - 15
Fire resistant of the cables, min, not less 180