Products

Search by features


VVG, AVVG, VVGE, AVVGE, VBShV, AVBShV, according to specification 16-705.4992010
specification 16-705.4992010

Conductor

Aluminum or copper core, single-wire or multi-wire, circular or sector-shaped form, 1 or 2 class according to GOST 22483.

Nominal cross-section area of main conductors, mm2

From 1.5 to 1000

Insulation

PVC- compound (colour coded conductor).

Stranding

Insulated conductors 2, 3, 4 and 5 core cables twisted in slotted core.

Inner sheath

Is made by extrusion with the filling exterior gaps between insulated conductors or for the unarmored cables with copper conductors by the taping with the PVC tapes, or nonwoven fabrics filling exterior gaps between insulated conductors insulating cords (bundles).

Screen

For VVGE, AVVGE is made in the form of taping with the copper tapes or by the agreement with a customer of copper wires and helically superimposed copper tape.

Cable armoring

For VBShV, AVBShV is made by taping with two steel galvanized tapes.

Oversheath or protective covering

PVC-compaund.

The cables are designed for transmission and distribution of electricity in fixed electrical installations on a nominal alternating voltage 0,66, 1 and 3 kV, frequency - 50 Hz.

Cables of types VVG, AVVG, VVGE, AVVGE, VBShV, AVBShV are designed for laying single cable lines in cable installations and premises.

Cables of types VBShV, AVBShV in a single-conductor modification is designed for use in DC voltage.

The class of fire hazard of the cables is according to GOST 31565 01.8.2.5.4.

Nominal voltage, kV 0,66; 1 and 3
Ambient temperature during cable operation, °С от – 50 до + 50
Minimum bending radius, diameters of cable for multi-core 7,5
for single-core 10
The cables are laid at temperature (without preheat), °С not below - 15

TABLE 1

Nominal voltage of cables, number and nominal cross-section of conductors

* - for operation in dc voltage only

** -for cables with the copper screen only

 

Type of cable Number of conductors Nominal cross-section
of main conductors, mm2
Nominal voltage of cable, kV
0,66 1 3
VVG, VVGE 1 1,5 - 50 1,5 - 1000 (1,5 - 1000)**
3,4 1,5 - 400  
2,5 1,5 - 240  
AVVG, AVVGE 1 2,5 - 50 2,5 - 1000 (2,5 - 1000)**
3,4 2,5 - 400  
2,5 2,5 - 240  
VBShV 1 (10 - 630)*  
3 1,5 - 50 1,5 - 400 6-240
4  
2,5 1,5 - 240  
AVBShV 1 (16 - 630)*  
3 2,5 - 50 2,5 - 400 10-240
4  
2,5 2,5 - 240  

 

TABLE 2

Conductors are made single- or multywire according to the table

Name of conductor Nominal cross-section of conductor, mm2
circular sector-shaped
copper aluminum copper aluminum
Однопроволочная 1,5 - 50 2,5 - 300 25 - 400
Многопроволочная 16 - 1000 25 - 1000 25 - 400 25 - 400

 

TABLE 3

Cross-section of screen made of copper wires

Name

Nominal cross-section of conductor, mm2

Main conductors

4 6 10 16 25 35 50 70

Screen

4 6 10 16 16 16 25 35

Name

Nominal cross-section of conductor, mm2

Main conductors

95 120 150 185 240 300 400

Screen

50 70 70 95 120 150 185
You can create an application yourself. Using the "Add brand manually" button, select the required cable brand and specify the quantity. After submitting the form, our managers will contact you and clarify the details of the order.

« * »  - required fields


FULL NAME:*

E-mail:*

Telephone:*

A comment:

Attach file