Products

Search by features


PPGng(A)-FRHF, PPGЕng(A)-FRHF, PvPGng(A)-FRHF, PvPGEng(A)-FRHF, according to specifications 16.K71-339-2014
specifications 16.K71-339-2014

Conductor

Copper, single-wire or multi-wire core, of circular or sector-shaped form, of the 1 or 2 class according to GOST 22483 with the cross-section from 1.5 to 1000mm2.

Thermal barrier for CCC (current-carrying conductor)

The lapping with two mica tapes.

Insulation

For cables of types PPGng(A)-FRHF and PPGЕng(A)-FRHF is made of halogen-free polymer composition, for cables of types PvPGng(A)-FRHF and PvPGEng(A)-FRHF of XLPE.

Core arrangement

Insulated conductors of 2, 3, 4 and 5 core cables are twisted in a cable core. Color coded.

Inner sheath

Of halogen-free polymer composition.

Taping

For cables of types PvPGng(A)-FRHF and PvPGEng(A)-FRHF with the cross-section up to 50 mm2 and more is made of mica tape or one fiber glass tape.

Screen

For cables of types PPGЕng(A)-FRHF and PvPGEng(A)-FRHF is made of lapping with copper tapes. It is allowed screen of copper wires and a spirally imposed copper tape.

Over sheath

Of halogen-free polymer composition.

The cables are designed for transmission and distribution of electric power and electric signals in stationary electric units on the nominal alternating voltage 0.66 and 1kV and frequency 50 Hz.

The cables are used for group installation of cable power lines of safety systems, wiring circuits of fire safety, wiring circuits of the surgical departments of hospitals, circuits of emergency electric power of equipment, functioning in case of fire, in the absence of danger of mechanical damage during operation.

The cable is manufactured for general application and application at nuclear power plants (NPP) outside the hermetic area in the systems NPP of class 2 according to classification ОПБ 88/97 (ПНАЭ Г-01-011).

The class of fire hazard of the cables according to GOST 31565 П1б.1.1.2.1.

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, °С from – 50 to + 50
Minimum bending radius, diameters of cable for multi-wire 7,5
for single-wire and flat 10
The cables are laid at temperature (without preheat), °С, not below - 15
Fire resistant of the cables, min, not less 180