VVGg-KhL, AVVGg-KhL, VVGEg-KhL, AVVGEg-KhL, VBShvg-KhL, AVBShvg-KhL, according to specification 16.K121-017-2011
Specifications 16.K121-017-2011

Conductor

Copper or aluminum core, single-wire or multiwire, circular or sector-shaped form of the 1 or 2 class according to GOST 22483.

Insulation

PVC- compound (color coded conductor).

Stranding

Insulated conductors of 2, 3, 4, 5 or 6 core cables twisted with water blocking materials.

Inner sheath

It is made by extrusion with filling of exterior gaps between insulated cores or for not armored cables with copper sector-shaped conductors with taping with PVC tapes with the filling of exterior gaps between insulated cores, insulating cords (bundles).

Screen

VVGEg-KhL, AVVGEg-KhL of copper tapes or copper wires and a copper tape. Cable armoring VBShVg-KhL, AVBShVg-KhL Two steel galvanized tapes are superimposed spirally.

Separation layer

VVGEg-KhL, AVVGEg-KhL, VBShVg-KhL, AVBShVg-KhL Water blocking tapes are superimposed by winding.

Cable sheath or jacket

PVC-compound.

The cables are designed for transmission and distribution of electric energy in stationary installations on a nominal alternating voltage 0,66 and 1kV, nominal frequency 50 Hz or direct voltage 1 and 1.5 kV respectively.

The cables are used for single installation of cable lines in cable constructions, open-air electrical installations (cable overpasses, arcades).

Cables VBShVg-KhL, AVBShVg-KhL are also used for laying in the ground. While manufacturing the cables we use the materials, which allow the cables to be resistant to low temperatures up to – 600C (degrees below zero) and water blocking materials as well, which allow the cables to be resistant to the longitudinal penetration of moisture and their use in conditions of high humidity.

The class of fire hazard of the cables is according to GOST 31565 01.8.2.5.4.

 

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, 0C from – 60 to + 50
Minimum bending radius, diameters of cable for multi-core 7,5
for single-core 10
The cables are laid at temperature (without preheat), 0C not below - 15

TABLE 1

Nominal voltage of the cables, number and nominal cross-section of currentcarrying conductor

* – for operation in DC voltage only

Type of cable Number of conductors Nominal cross-section of main conductors, mm2
Nominal voltage, kV
0,66 1
VVGg-KhL 1 1,5 – 50 1,5 – 1000
 
VVGEg-KhL 2, 3, 4, 5 1,5 – 400
AVVGg-KhL 1 2,5 – 50 2,5 – 1000
 
AVVGEg-KhL 2, 3, 4, 5 2,5 – 400
VBShVg-KhL 1 (1,5 – 1000)*
2, 3, 4, 5 1,5 – 50 1,5 – 400
AVBShVg-KhL 1 (2,5 – 1000)*
2, 3, 4, 5 2,5 – 50 2,5 - 400

 

TABLE 2

Current-carrying conductors are manufactured singleor multi-wire in accordance with the table

Type of conductor Nominal cross-section of main conductors, mm2
Circular Sector-shaped
copper aluminum copper aluminum
singular 1,5 - 50 2,5 - 300 25 - 400
multi-wire 16 - 1000 25 - 1000 25 - 400 25 - 400

 

TABLE 3

Cross-section of copper wires

Designation Nominal cross-section of main conductors, mm2
Main conductors 1,5 2,5 4 6 10 16 25 35
Screen 1,5 2,5 4 6 10 16 16 16
Designation Nominal cross-section of main conductors, mm2
Main conductors 50 70 95 120 150 185 240 300 400
Screen 25 35 50 70 70 95 120 150 185