Products

Search by features


VVG-Png(A)-LS, AVVG-Png(A)-LS, according to specifications respectively, 16.K71-310-2001
specifications 16.К71-310-2001

Conductor

Copper or aluminum, single-wire, of circular form, of the 1 class according to GOST 22483.

Number of conductors

2 or 3

Nominal cross-section of the conductors, mm2

Copper – 1.5-16

Aluminum – 2.5-16

Insulation

PVC-compound of low flammability (color coded conductor).

Core arrangement

Insulated conductors laid in parallel in one flat.

Cable sheath

PVC-compound of low flammability

The cables VVG-Png(A)-LS and AVVG-Png(A)-LS are designed for transmission and distribution of electric energy in stationary electric installations on alternating voltage 0,66 and 1kV and frequency 50 Hz.

The cables are used for electrical installations in residential and public buildings.

The cables are designed for use in cable structures and premises, including the objects where nuclear energy is used in the AC systems of classes 3 and 4 according to classification ОПБ-88 (ПНАЭГ–01-011-97).

The class of fire hazard of the cables according to GOST 31565 П1б.8.2.2.2.

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, °С from – 50 to + 50
Minimum bending radius, diameters of cable (for the smallest measurements)  10
The cables are laid at temperature (without preheat), °С, not below - 15
Smoke generation in the test cell not more than 50 %

TABLE 1

Nominal voltage of the cables, number and nominal cross-section of current-carrying conductor

Type of cable Number of conductors Nominal cross-section of main conductors, mm2
Nominal voltage, kV
0,66 1
VVG-Png(A)-LS 2, 3 1,5 – 16 1,5 – 16
AVVG-Png(A)-LS 2, 3 2,5 – 16 2,5 – 16