Products

Search by features


ВБВгнг(А)-LS (VBVgng(A)-LS)

ВБВгнг(А)-LS (VBVgng(A)-LS)
Price on request
₽0
By category
Force cables
Voltage
6000
In execution
Flame retardant (-ng(А)) / With low smoke and gas emission (-LS) / Armored
Insulation
Copper
Shell
PVC insulation
Core material
Flexible PVC
Number and nom, cross-section of CCC and screens, nxmm2, external diameter, mm, weight of 1km of cable, kg
VBVgng(A)-LS
Cables with circular conductors
with copper conductor
Number and nom. cross-section of CCC and screens, nxmm2 External diameter, mm Weight of 1km of cable, kg
3x16/16 39 2320
3x25/16 41,9 2770
3x35/16 44,2 3222
3x50/16 47,3 3899
3x70/16 51 4725
3x95/16 54,5 5697
3x120/16 57,9 6726
3x150/25 61 7833
3x185/25 64,9 9112
3x240/25 70,7 11286
VBVgng(A)-LS
Cables with sector-shaped conductors
with copper conductor
Number and nom. cross-section of CCC and screens, nxmm2 External diameter, mm Weight of 1km of cable, kg
3x35/16 41,1
3x50/16 43,5 3227
3x70/16 46,2 3940
3x95/16 48,9 4760
3x120/16 51,5 5581
3x150/25 54 6613
3x185/25 57,4 7767
3x240/25 61,6 9491

₽0 for 1 м

Quantity
- + м Add to cart

SCOPE AND PURPOSE

The cables are designed for transmission and distribution of electric power at the stationary installation on the nominal alternating voltage 6kV of frequency 50 Hz for networks with the earthed and insulated neutral.

The climate modification УХЛ, categories of location 1 and 5 according to GOST 15150, including installation in the ground.

The class of fire hazard of the cables according to GOST 31565 П1б.8.2.2.2.

STRUCTURE

Conductor

Copper, single-wire or multi-wire, of circular or sector-shaped form, of the 1 or 2 class according to GOST 22483.

Insulation

Is made of PVC-compound of low fire hazard (color coded conductor).

Core arrangement

Insulated conductors of multi-core cables are twisted in a cable core.

Inner sheath

It is made by extrusion with PVC-compound of low fire hazard or chalk-filled non-cured rubber with the filling of outer gaps between insulated conductors. It is possible to fill the outer gaps between circular insulated cores with the bundles of with the lapping of fastening tape and extrusion inner sheath. It is allowed to wrap the cable core with the tapes of polymer material.

Taping

Layer of water blocking tapes.

Screen

Of copper wires and a spirally imposed copper tape. It is allowed the application of the screen with copper tapes.

Separating layer

Layer of water blocking tapes.

Bedding

Of PVC-compound of low fire hazard.

Cable armoring

Is lapped helically with two steel, galvanized tapes.

Over sheath

Of PVC-compound of low fire hazard.

By category
Force cables
Voltage
6000
In execution
Flame retardant (-ng(А)) / With low smoke and gas emission (-LS) / Armored
Insulation
Copper
Shell
PVC insulation
Core material
Flexible PVC
Number and nom, cross-section of CCC and screens, nxmm2, external diameter, mm, weight of 1km of cable, kg
VBVgng(A)-LS
Cables with circular conductors
with copper conductor
Number and nom. cross-section of CCC and screens, nxmm2 External diameter, mm Weight of 1km of cable, kg
3x16/16 39 2320
3x25/16 41,9 2770
3x35/16 44,2 3222
3x50/16 47,3 3899
3x70/16 51 4725
3x95/16 54,5 5697
3x120/16 57,9 6726
3x150/25 61 7833
3x185/25 64,9 9112
3x240/25 70,7 11286
VBVgng(A)-LS
Cables with sector-shaped conductors
with copper conductor
Number and nom. cross-section of CCC and screens, nxmm2 External diameter, mm Weight of 1km of cable, kg
3x35/16 41,1
3x50/16 43,5 3227
3x70/16 46,2 3940
3x95/16 48,9 4760
3x120/16 51,5 5581
3x150/25 54 6613
3x185/25 57,4 7767
3x240/25 61,6 9491