KPEPng(A)-HF, KGPEPng(A)-HF, KUGPPng(A)-HF, KUGPPEng(A)-HF, KUGPPEPng(A)-HF, KUGPEPng(A)-HF, KUGEPPng(A)-HF, KUGEPPEng(A)-HF, KUGEPPEPng(A)-HF, according to specifications 16.K71-338-2004
specifications 16.K71-338-2004

Current-carrying conductor

Copper, multi-wire or single-wire.

For KPEPng(A)-HF of the 1 class, for the rest ones of the 4 class according to GOST 22483- 2012.

Insulation

Halogen-free polymer composition.

Twisting in pairs.

For cables with pair twisting the insulated conductors are twisted in pairs.

Screen over conductor

For KUGEPPng(A)-HF; KUGEPPEng(A)-HF and KUGEPPEPng(A)-HF – a screen of copper galvanized wire over the insulated conductor or a pair of insulated conductors.

Separating layer

For KUGPEPng(A)-HF of halogen-free polymer composition.

For the rest ones – taping with PET–E film.

Inner sheath

For KUGPPEPng(A)-HF and KUGEPPEPng(A)-HF - halogen-free polymer composition.

Screen

For KPEPng(A)-HF, KGPEPng(A)-HF – a common screen in the form of foil, composite flexible material under the sheath, copper galvanized contact wire is laid under the screen.

For KUGPPEPng(A)-HF and KUGEPPEPng(A)-HF – a common screen in the form of braid of copper galvanized wire.

For KUGPEPng(A)-HF - a common screen in the form of braid of copper wire.

Over sheath

Halogen-free polymer composition.

Screen

For KUGPPEng(A)-HF and KUGEPPEng(A)-HF a common screen in the form of braid of copper galvanized wire over the sheath.

The cables are designed for transmission OF ELECTRIC SIGNALS and distribution of electric energy in control circuits, alarm, communications, and unit connections of voltage 250, 380 and 1000V of alternating current of frequency up to 200 kHz or at voltage correspondingly 350, 750 and 1500V of direct current.

The cables are manufactured for general industrial use and nuclear power stations at usage out of under containment zone of NPP.

The climate modification B, categories of location – 5, according to GOST 15150-69.

The class of fire hazard of the cables according to GOST 31565- 2012  П1б.8.1.2.1.

Nominal voltage, kV 250; 380; 1000
Ambient temperature during cable operation, °С from – 50 to +50
Minimum bending radius, diameters of the cable for multi-wire 7,5
Minimum bending radius, diameters of the cable for single-wire 10
Ambient temperature for laying of the cables (without preheat), °С, not below not below -15

Table 1

Nominal voltage of cables, number and nominal cross-section of current-carrying conductors

Type of cable Nominal diameter of conductor, mm Nominal crosssection of con– ductors (mm2) Number of con– ductors or pairs Nominal alternating voltage, V
KPEPng(A)-HF 0,5; 0,6; 0,8; 1,13; 1,38 _ 1х2; 2х2; 4х2; 6х2;
8х2; 10х2; 12х2;
14х2; 16х2; 20х2;
24х2; 30х2; 40х2;
50х2; 60х2; 80х2;
100х2
250
KGPEPng(A)-HF, KUGPPng(A)-HF, KUGPPEng(A)-HF, KUGPPEPng(A)-HF, KUGPEPng(A)-HF, KUGEPPng(A)-HF, KUGEPPEng(A)-HF, KUGEPPEPng(A)-HF _ 0,35; 0,5; 0,75; 1,0;
1,5; 2,5
1, 2, 3, 4, 7, 10, 12,
14, 19, 24, 27, 30,
37, 52
1х2; 2х2; 4х2; 6х2;
8х2; 10х2; 14х2;
16х2; 20х2; 24х2;
30х2; 37х2; 52х2
380, 1000