Products

Search by features


RPGng(A)-FRHF, RPGEng(A)-FRHF, RPG-Png(A)-FRHF, according to specifications 16.K121-026-2013
specifications 16.K121-026-2013

Number of conductors

For RPGng(A)-FRHF and RPGEng(A)-FRHF from 1 to 5.

For RPG-Png(A)-FRHF 2 or 3.

Conductor

Copper, of circular form, single-wire core with the cross-section from 1.5 to 16mm2 or multiwire core with the cross-section from 10 to 16mm2.

Insulation

Ceramic forming silicon rubber.

Core arrangement and twisting

For cables of types RPGng(A)-FRHF and RPGEng(A)-FRHF insulated conductors of 2 - 5 core cables twisted in a cable core.

For cables of type RPG-Png(A)-FRHF insulated cores are arranged in parallel in one flat.

Inner sheath

For cables of types RPGng(A)-FRHF and RPGEng(A)-FRHF halogen-free polymer composition.

Screen

For the type RPGEng(A)-FRHF - copper tape.

Over sheath

Halogen-free polymer composition.

The cables are designed for transmission and distribution of electric power at the stationary installation on the nominal alternating voltage 0.66 and 1kV and frequency 50 Hz.

The cables do not spread combustion at the group stationary installation of cable power lines in the absence of danger of mechanical impact on the cable and it keeps working in case of fire during 180 minutes.

The cables are designed for wiring and emergency power circuits of equipment (current collectors), in residential and public buildings, in the surgical departments of hospitals, in the office premises, equipped with computer and micro processor devices, spectacular complexes and sports facilities, as well as in other objects with the high demand of fire safety.

The cables of types RPG-Png(A)-FRHF are used for installation under plaster, where a seal is not required when entering.

The class of fire hazard of the cables according to GOST 31565 П1б.1.1.2.1.

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, °С from – 40 to + 60
Minimum bending radius, diameters of cable for multi-wire 7,5
for single-wire and flat 10
The cables are laid at temperature (without preheat), °С, not below - 15
Fire resistant of the cables, min, not less 180
You can create an application yourself. Using the "Add brand manually" button, select the required cable brand and specify the quantity. After submitting the form, our managers will contact you and clarify the details of the order.

« * »  - required fields


FULL NAME:*

E-mail:*

Telephone:*

A comment: