specification 27.32.13-038-53972660-2020

Conductor

The conductors of cables should be multi-wired, flexible, round, made of copper and should meet the requirements of GOST 22483:

- for cables with cross section of conductor from 0,5 up to 4 mm² - 4 class of conductor;

- for cables with cross section of conductor from 6 up to 95 mm² - 3 class of conductor.

Insulation

Polyethylene composition

 (Color coded conductor, for single-core cables – white (uncolored) conductor)

Core arrangement

Insulated conductors of different colors, twisted in a cable core.

Over sheath

PVC-compound


Flexible power cables with no fire safety requirements

Flexible power cables for speciolized purposes with insullation made of polyethylene composition and over sheath made of pvc-compound

The cables are designed for connection to the electrical networks in a fixed position for voltage of 380, 450 and 660 V with alternating current frequency up to 400 Hz of water-submersible electric motors, long-term operating under the pressure of water of artesian wells up 7,09х106 Pa (70 kgf/cm2).

The class of fire hazard of the cables according to GOST 31565 О2.8.2.5.4

Nominal alternating voltage, kV

380, 450, 660

Ambient temperature during cable operation, °С

from –40

to +70

Relative humidity at ambient temperature up to + 35 °С, including outdoor installation, %

up to 98

Operating atmosphere pressure

Up to 7,09х106 Pa (70 kgf/cm2)

Minimum bending radius, mm

10Dн

The cables are laid at temperature (without preheat), °С, not below

-15

Durably allowable temperature of heating of conductors during operation, not above, °С

+70