PuVng(A)-LS, PuGVng(A)-LS, PuVVng(A)-LS, PuGVVng(A)-LS, KuVVng(A)-LS, KuGVVng(A)-LS, according to specifications 16-705.502-2011
specifications 16-705.502-2011
Type of wire or cable Current-carrying conductor Number of insulated conductors Range of cross-sections, mm2 nsulation Sheath
KuGVVng(A)-LS Copper, of the 5 class 2, 3, 4, 5 0,75-50 PVC-compound PVC-compound
KuVVng(A)-LS Copper, of the 1 and 2 class 2, 3, 4, 5 0,75-50 PVC-compound PVC-compound
PuGVVng(A)-LS Copper, of the 5 class 1 0,5-400 PVC-compound PVC-compound
PuVVng(A)-LS Copper, of the 1 and 2 class 1, 2, 3 0,5-400 (1 core) 0.5-4.0 (2 and 3 cores) PVC-compound PVC-compound
PuGVng(A)-LS Copper, of the 5 class 1 0,5-400 PVC-compound -
PuVng(A)-LS Copper, of the 1 and 2 class 1 0,5-400 PVC-compound -

The wires and cables are intended for distribution of electric energy in the electric installations at stationary laying in lighting and power electric networks as well as for installation of electrical equipment, machines, tools and other machines, indoor electric settings, for installation outdoors and in the industrial premises, steel pipes, and hollow channels of building structures, hidden under the plaster lining.

The wire used for the installation of electrical circuits, power motors, various industrial and laboratory equipment, and portable devices.

The wires of types PuVng(A)-LS, PuGVng(A)-LS, PuVVng(A)-LS, PuGVVng(A)-LS are intended for operation on the nominal alternating voltage up to and including 450/750V of nominal frequency up to 400 Hz or on direct voltage up to and including 1000V.

The cables of types KuVVng(A)-LS and KuGVVng(A)-LS are intended for operation on nominal alternating voltage up to and including 300/500V and of nominal frequency up to 400 Hz or direct voltage up to and including 1000V.

The wires and cables are used for group installation on category A.

The class of fire hazard of the cables according to GOST 31565 - П1Б 8.2.2.2.

Ambient temperature during cable operation, °С from - 40 to + 65
Minimum bending radius, of outer diameters -for wires of types PuVng(A)-LS and PuVVng(A)-LS and cables of type KuVVng(A)-LS 10
-for wires of types PuGVng(A)-LS and PuGVVng(A)-LS and cables of type KuGVVng(A)-LS 5
The ambient temperature for installation of the cables (without preheat), 0C not below - 15
Durably allowable temperature of heating of conductors during operation, 0C + 70
Smoke generation in the test cell not more than 50%