Products

Search by features


ПвБПнг(А)-FRHF (PvBPng(A)-FRHF)

ПвБПнг(А)-FRHF (PvBPng(A)-FRHF)
Price on request
₽0
By category
Force cables
Voltage
660 / 1000
In execution
Flame retardant (-ng(А)) / Halogen free (-HF) / Fireproof (-FR) / Armored
Insulation
Copper
Shell
Crosslinked polyethylene
Core material
Polymer composition
Number and nom, cross-section of CCC and screens, nxmm2, external diameter, mm, weight of 1km of cable, kg
Number of conductors, nominal cross-section (mm2), construction, voltage (kV) Calculated diameter of cable, mm Calculated weight of cable, kg/km
4х70мс(N)-1 38,8 3935
4х95мс(N)-1 42,6 5052
4х120мс(N)-1 46,7 6188
4х150мс(N)-1 51,3 7681
4х185мс(N)-1 56,5 9390
4х240мс(N)-1 61,9 11774

₽0 for 1 м

Quantity
- + м Add to cart

SCOPE AND PURPOSE

The cables are designed for transmission and distribution of electric power in the fixed networks on the nominal alternating voltage 0.66 and 1kV and nominal frequency 50 Hz.

The cables are used for group installation of cable power lines of safety systems, wiring circuits of fire safety, (the wiring circuits of systems of fire alarm, power of pumps of fire suppression, illuminations of emergency exits and escape routes, smoke removal systems and ventilation, evacuation lifts).

For wiring in the surgical departments of hospitals, of the wiring circuits of emergency power supply of the equipment (current collectors), functioning in case of fire. It keeps working in case of fire during 180 (FE180) or 240 (FE240) minutes.

The class of fire hazard of the cables according to GOST 31565 П1б.1.1.2.1.

STRUCTURE

Conductor

Copper, single-wire or multi-wire core, of circular or sector-shaped form, of the 1 or 2 class according to GOST 22483 with the cross-section from 1.5 to 1000mm2

Thermal barrier for CCC (current-carrying conductor)

The overlapping with two mica tapes.

Insulation

XLPE.

Core arrangement

Insulated conductors of 2, 3, 4 and 5 core cables are twisted in a cable core.

Inner sheath

Halogen-free polymer composition.

Thermal barrier

Lapped with mica or fiber glass tapes.

Additional thermal barrier (for “FE240”)

Taped with fiber glass mica tapes.

Cable armoring

For cables of types PvBPng-FRHF is laid helically with two steel, galvanized tapes over the thermal barrier.

Over sheath or jacket

Of halogen-free polymer composition.

By category
Force cables
Voltage
660 / 1000
In execution
Flame retardant (-ng(А)) / Halogen free (-HF) / Fireproof (-FR) / Armored
Insulation
Copper
Shell
Crosslinked polyethylene
Core material
Polymer composition
Number and nom, cross-section of CCC and screens, nxmm2, external diameter, mm, weight of 1km of cable, kg
Number of conductors, nominal cross-section (mm2), construction, voltage (kV) Calculated diameter of cable, mm Calculated weight of cable, kg/km
4х70мс(N)-1 38,8 3935
4х95мс(N)-1 42,6 5052
4х120мс(N)-1 46,7 6188
4х150мс(N)-1 51,3 7681
4х185мс(N)-1 56,5 9390
4х240мс(N)-1 61,9 11774