KуРЭВнг(А)-FRLS (KuRЕVng(A)-FRLS) Russian analogue of Bitflame S(ST) FE180/E30 Low Smoke KуГРЭВнг(А)-FRLS (KuGREVng(A)-FRLS) Russian analogue of Bitflame SL(ST) FE180/E30 Low Smoke
specifications 16-K121-025-2013
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Number of conductors
From 2 to 5
Conductor
Copper, single-wire of the 1 class (for cross-sections from 0.5 to and including 10 mm2), or multi-wire of circular form of the 2 class (for cross-sections 16 mm2), or for cables with the flexible conductors of the 5 class (for cross-sections from 0.5 up to 16 mm2)
Insulation
Ceramics-forming rubber.
Core arrangement
Insulated conductors of 2-5 core cables are twisted.
Inner sheath
PVC-compound of low fire hazard.
Screen
Aluminum tape with the contact conductor of copper, galvanized wire.
Over sheath
PVC-compound of low fire hazard.
The cables are intended for electric installations at stationary laying in lighting and power electric networks as well as for installation of electrical equipment, machines, tools and other machines on the nominal alternating voltage up to 220/380V of frequency up to 400 Hz or on direct voltage up to and including 700V.
The cables do not spread combustion at group stationary installation of cable lines, in the absence of mechanical effects and keep working when exposed to flame not less than 180 minutes.
They are designed for wiring and networks of the wiring circuits of emergency power supply of the equipment (current collectors), in residential and public buildings, in the surgical departments of hospitals, in office premises, equipped with computer and microprocessor devices, entertainment complexes and sports facilities, as well as at other objects with the high demand of fire safety.
The class of fire hazard of the cables according to GOST 31565 - П1Б1.2.2.2.
Operating voltage, V | 220/380 | |
Ambient temperature during cable operation, °С | from - 40 to + 50 | |
Minimum bending radius at laying of the cables, of outer diameters of the cable | -for cables with the conductors of the 1 and the 2 class | 10 |
-for cables with flexible conductors | 5 | |
The ambient temperature for installation of the cables (without preheat), 0C not below | - 15 | |
Fire resistance of the cables, min, not less | 180 | |
Smoke generation in the test cell | not more than 50% |
To make an order
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
«*»- required fields