КуРЭВКВнг(А)-FRLS (KuREVKVng(A)-FRLS) Russian analogue of H07SC4V(Z)V-U FE180 Low Smoke КуГРЭВКВнг(А)-FRLS (KuGREVKVng(A)-FRLS) Russian analogue of H07SC4V(Z)V-K FE180 Low Smoke
specifications 16-K121-025-2013
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Number of conductors
From 2 to 5
Current-carrying conductor
Copper, single-wire of the 1 class (for cross-sections from 0.5 to and including 10mm2), or multi-wire of circular form of the 2 class (for cross-sections 16mm2), or for cables with the flexible conductors of the 5 class (for cross-sections from 0.5 up to 16mm2)
Insulation
Ceramics-forming rubber.
Core arrangement and twisting
Insulated conductors of 2- 5 core cables are twisted.
Inner sheath
PVC-compound of low fire hazard.
Screen
Alum polymer tape with a contact conductor of copper, galvanized wire.
Separating layer
PVC-compound of low fire hazard.
Cable armoring
Galvanized steel-wire braid.
Over sheath
PVC-compound of low fire hazard
The cables are intended for electric installations at stationary laying in lighting and power electric networks as well as for installation of electrical equipment, machines, tools and other machines on the nominal alternating voltage up to 220/380V of frequency up to 400 Hz or on direct voltage up to and including 700V.
The cables do not spread combustion at group stationary installation of cable lines, in the absence of mechanical effects and keep working when exposed to flame not less than 180 minutes.
They are designed for wiring and networks of the wiring circuits of emergency power supply of the equipment (current collectors), in residential and public buildings, in the surgical departments of hospitals, in office premises, equipped with computer and microprocessor devices, entertainment complexes and sports facilities, as well as at other objects with the high demand of fire safety in case of danger of mechanic damage in process of operation, if the cable is not exposed to significant tensile force, as well as requirements for protection from rodents.
The class of fire hazard of the cables according to GOST 31565 - П1Б 1.2.2.2.
Operating voltage, V | 220/380 | |
Ambient temperature during cable operation, °С | from - 40 to + 50 | |
Minimum bending radius at laying of the cables, of outer diameters of the cable | -for cables with the conductors of the 1 and the 2 class | 10 |
-for cables with flexible conductors | 5 | |
The ambient temperature for installation of the cables (without preheat), 0C not below | - 15 | |
Fire resistance of the cables, min, not less | 180 | |
Smoke generation in the test cell | not more than 50 % |