КМПвВнг(А)-FRLS (KMPvVng(A)-FRLS) - Russian analogue of JE-2XY-Bd КМПвВЭнг(А)-FRLS (KMPvVEng(A)-FRLS) - Russian ana logue of JE-2XYC КМПвВЭВнг(А)-FRLS (KMPvVEVng(A)-FRLS) - Russian ana logue of JE-2XYCY-Bd КМПвЭВнг(А)-FRLS (KMPvEVng(A)-FRLS) - Russian ana logue of JE-2XCY-Bd КМПвЭВЭнг(А)-FRLS (KMPvEVEng(A)-FRLS) - Russian ana logue of JE-2XCYC-Bd КМПвЭВЭВнг(А)-FRLS (KMPvEVEVng(A)-FRLS) - Russian analogue of JE-2XCYCY-Bd

KMPvVng(A)-FRLS, KMPvVEng(A)-FRLS, KMPvVEVng(A)-FRLS, KMPvEVng(A)-FRLS, KMPvEVEng(A)-FRLS, KMPvEVEVng(A)-FRLS, according to specifications 16.K71-337-2004

specifications 16.K71-337-2004

Construction Application area Technical data Calculated data To order
To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

Current-carrying conductor

Copper, multi-wire of circular form, of the 3 or 4 class according to GOST 22483.

Thermal barrier

Taping with two mica tapes.

Insulation

XLPE (color or digital coded conductors).

Screen

For cables of types KMPvEVng(A)-FRLS, KMPvEVEng(A)-FRLS and KMPvEVEVng(A)-FRLS insulated conductors are screened or screened in pairs by braiding with copper galvanized or copper wires.

Core arrangement and twisting

Insulated conductors, screened cores and screened pairs are twisted in a cable core by concentric layer.

Taping

Of PET or polyamide film.

Inner sheath

PVC-compound of low fire hazard.

Overall screen

For cables of types KMPvVEng(A)-FRLS, KMPvEVEng(A)-FRLS and KMPvEVEVng(A)-FRLS is made in the form of braiding of copper, galvanized wires.

For cables of types KMPvVEVng(A)-FRLS, KMPvEVEng(A)-FRLS and KMPvEVEVng(A)-FRLS a screen of copper wires is allowed.

Taping

Of PET-E or polyamide film for cables of types KMPvVEVng(A)-FRLS and KMPvEVEVng(A)-FRLS.

Over sheath

PVC-compound of low fire hazard.

The cables are designed for transmission and distribution of nominal electric energy stationary electric installations on nominal alternating voltage 0,5 and 1 kV and frequency up to 100 Hz or correspondingly on direct voltage 0.75 and 1.5 kV.

The cables are manufactured for general industrial use and nuclear power stations.

The cables don’t spread combustion at group installation.

The cables are designed for use in cable structures and premises, including objects which use nuclear power, in the systems of NPP of class 2 according to classification of  ОПБ-88/97 (ПНАЭ Г – 01-011).

The climate modification B, categories of location 1– 5, according to GOST 15150-69.

The class of fire hazard of the cables according to GOST 31565 - П1б.1.2.2.2

Nominal voltage, kV 0,5; 1
Ambient temperature during cable operation, °С from – 50 to + 65
Ambient temperature for laying and installation of the cables (without preheat), °С, not below  -15
Minimum bending radius, diameters of the cable 12
Fire resistance of the cables, min, not less 180
Smoke generation in the test cell not more than 50 %

Table 1

Nominal voltage of cables, number and nominal cross-section of current-carrying conductors

* Cable with screened pairs of conductors

Type of cable Nominal cross-section of conductors (mm2) Number of conductors Nominal alternative voltage, V
KMPvVng(A)-FRLS 0,35 1, 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500
0,5 – 1,5 1, 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500, 1000
2,5 1, 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37 500, 1000
KMPvVEng(A)-FRLS, KMPvVEVng(A)-FRLS 0,35 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500
0,5 – 1,5 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500, 1000
2,5 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37 500, 1000
KMPvEVng(A)-FRLS, KMPvEVEng(A)-FRLS, KMPvEVEVng(A)-FRLS 0,35 – 1,0 2, 3, 4, 7, 12, 14, 19, 24, 27, 37, 52 500
0,35; 0,75 16х2э*, 19х2э*, 37х2э* 500
1,5 2, 3, 4, 7, 12, 14, 19, 24, 27, 37, 52 500, 1000

To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

«*»- required fields