КМПВнг(А)-LS (KMPVng(A)-LS) - Russian analogue of JE-2YY-Bd КМПВЭнг(А)-LS (KMPVEng(A)-LS) - Russian analogue of JE-2Y(St)Y-Bd КМПВЭВнг(А)-LS (KMPVEVng(A)-LS) - Russian analogue of JE-2Y(St)Yv-Bd КМПЭВнг(А)-LS (KMPEVng(A)-LS) - Russian analogue of JE-2Y(St)YY-Bd КМПЭВЭнг(А)-LS (KMPEVEng(A)-LS) - Russian analogue of JE-2Y(St)Y(St)-Bd КМПЭВЭВнг(А)-LS (KMPEVEVng(A)-LS)- Russian analogue of JE-2Y(St)YY(St)-Bd

KMPVng(A)-LS, KMPVEng(A)-LS, KMPVEVng(A)-LS, KMPEVng(A)-LS, KMPEVEng(A)-LS, KMPEVEVng(A)-LS, according to specifications 16.K71-310-2001

specifications 16.K71-310-2001

Construction Application area Technical data Calculated data To order
To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

Current-carrying conductor

Copper, multi-wire of circular form, of the 3 or 4 class according to GOST 22483.

Insulation

Polyethylene (color or digital coded conductors).

Screen

For KMPEVng(A)-LS, KMPEVEng(A)-LS and KMPEVEVng(A)-LS insulated conductors are screened or screened in pairs with copper wires or by braiding with copper galvanized or non-galvanized wires.

Core arrangement and twisting

Insulated conductors, screened cores and screened pairs are twisted in a cable core by concentric layer in different directions.

Taping

Of fiberglass tape or mica tape or polyamide film. It is allowed longitudinal wrapping.

Over sheath

PVC-compound of low fire hazard.

Overall screen

For KMPVEng(A)-LS, KMPEVng(A)-LS, KMPEVEng(A)-LS and KMPEVEVng(A)-LS insulated conductors are screened or screened in pairs with copper wires or by braiding with copper galvanized or non galvanized wires.

Taping

For KMPVEVng(A)-LS and KMPEVEVng(A)-LS of PET or polyamide film.

Belt insulation

Spiral overlapping with PET-E tapes.

Second over sheath

For cables KMPVEVng(A)-LS and KMPEVEVng(A)-LS PVC-compound of low fire hazard.

The cables are designed for transmission and distribution of nominal electric energy in stationary electric installations on alternating voltage 0,5 and 1 kV and frequency not more than 50 Hz or correspondingly on direct voltage 0.75 and 1.5 kV

The cables are manufactured for general industrial use and nuclear power stations.

The cables don’t spread combustion at group installation.

The cables are designed for use in cable structures and premises, including objects which use nuclear power, in the systems of NPP of class 3 and 4 according to classification of ОПБ-88 (ПНАЭ Г – 01-011).

The class of fire hazard of the cables according to GOST 31565 - П1б.8.2.2.2

Nominal voltage, kV 0,5; 1
Ambient temperature during cable operation, °С from – 50 to + 65
The ambient temperature for laying and installation of the cables (without preheat), 0C not below -15
Minimum bending radius, diameters of the cable 12
Smoke generation in the test cell not more than 50 %

Table 1

Nominal voltage of cables, number and nominal cross-section of current-carrying conductors

* Cable with screened pairs of conductors

Type of cable Nominal cross-section of conductors (mm2) Number of conductors Nominal alternative voltage, V
KMPVng(A)-LS 0,35 1, 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500
0,5 – 1,5 1, 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500, 1000
2,5 1, 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37 500, 1000
KMPVEng(A)-LS, KMPVEVng(A)-LS 0,35 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500
0,5 – 1,5 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37, 52 500, 1000
2,5 2, 3, 4, 7, 10, 12, 14, 19, 24, 27, 30, 37 500, 1000
KMPEVng(A)-LS, KMPEVEng(A)-LS, KMPEVEVng(A)-LS 0,35 – 1,0 2, 3, 4, 7, 12, 14, 19, 24, 27, 37, 52 500
0,35; 0,75 16х2э*, 19х2э*, 37х2э* 500
1,5 2, 3, 4, 7, 12, 14, 19, 24, 27, 37, 52 500, 1000