ВВГгнг(А)-LS (VVGgng(A)-LS) - Russian analogue of NYSBY Flame Retardant Low Smoke

ВВГгнг(А)-LS (VVGgng(A)-LS) - Russian analogue of NYSBY Flame  Retardant Low Smoke

Description Add to order

SCOPE AND PURPOSE

The cables are designed for transmission and distribution of electric power at the stationary installation on the nominal alternating voltage 6kV of frequency 50 Hz for networks with the earthed and insulated neutral.

The climate modification УХЛ, categories of location 1 and 5 according to GOST 15150, including installation in the ground.

The class of fire hazard of the cables according to GOST 31565 П1б.8.2.2.2.

STRUCTURE

Conductor

Copper, single-wire or multi-wire, of circular or sector-shaped form, of the 1 or 2 class according to GOST 22483.

Insulation

Is made of PVC-compound of low fire hazard (color coded conductor).

Core arrangement

Insulated conductors of multi-core cables are twisted in a cable core.

Inner sheath

It is made by extrusion with PVC-compound of low fire hazard or chalk-filled non-cured rubber with the filling of outer gaps between insulated conductors. It is possible to fill the outer gaps between circular insulated cores with the bundles of with the lapping of fastening tape and extrusion inner sheath. It is allowed to wrap the cable core with the tapes of polymer material.

Taping

Layer of water blocking tapes.

Screen

Of copper wires and a spirally imposed copper tape. It is allowed the application of the screen with copper tapes.

Separating layer

Layer of water blocking tapes.

Over sheath

Of PVC-compound of low fire hazard.

Cables with circular conductors
with copper conductor
Number and nom. cross-section of CCC and screens, nxmm2 External diameter, mm Weight of 1km of cable, kg
VVGgng(A)-LS 1x16/16 20 631
km
VVGgng(A)-LS 1x25/16. 21,3 743
km
VVGgng(A)-LS 1x35/16 22,4 862
km
VVGgng(A)-LS 1x50/16 23,5 1033
km
VVGgng(A)-LS 1x70/16 25 1254
km
VVGgng(A)-LS 1x95/16 26,8 1522
km
VVGgng(A)-LS 1x120/16 28 1785
km
VVGgng(A)-LS 1x150/25 30,1 2178
km
VVGgng(A)-LS 1x185/25 31,9 2541
km
VVGgng(A)-LS 1x240/25 34,1 3097
km
VVGgng(A)-LS 1x300/25 36,3 3696
km
VVGgng(A)-LS 1x400/35 39,4 4767
km
VVGgng(A)-LS 1x500/35 42,1 5743
km
VVGgng(A)-LS 1x630/35 45,9 7041
km
VVGgng(A)-LS 1x800/35 49,6 8676
km
VVGgng(A)-LS 3x16/16 35 1607
km
VVGgng(A)-LS 3x25/16 37,9 1997
km
VVGgng(A)-LS 3x35/16 40,1 2400
km
VVGgng(A)-LS 3x50/16 43,1 2978
km
VVGgng(A)-LS 3x70/16 47 3767
km
VVGgng(A)-LS 3x95/16 50,5 4669
km
VVGgng(A)-LS 3x120/16 53,4 5586
km
VVGgng(A)-LS 3x150/25 57,1 6674
km
VVGgng(A)-LS 3x185/25 60,8 7875
km
VVGgng(A)-LS 3x240/25 65,5 9767
km
Cables with sector-shaped conductors
with copper conductor
Number and nom. cross-section of CCC and screens, nxmm2 External diameter, mm Weight of 1km of cable, kg
VVGgng(A)-LS 3x35/16 37,1
km
VVGgng(A)-LS 3x50/16 39,2 2425
km
VVGgng(A)-LS 3x70/16 41,9 3048
km
VVGgng(A)-LS 3x95/16 44,5 3812
km
VVGgng(A)-LS 3x120/16 47,5 4614
km
VVGgng(A)-LS 3x150/25 50 5593
km
VVGgng(A)-LS 3x185/25 52,9 6640
km
VVGgng(A)-LS 3x240/25 57,4 8321
km