ВБаШв-ХЛ (VBaShv-KhL) – Russian analogue of NYB(Al)Y Cold Resistance АВБаШв-ХЛ (AVBaShv-KhL) – Russian analogue of NAYB(Al)Y Cold Resistance ВКаШв-ХЛ (VKaShv-KhL) – Russian analogue of NYR(Al)Y Cold Resistance ВКШв-ХЛ (VKShv-KhL) – Russian analogue of NYRY Cold Resistance АВКШв-ХЛ (AVKShv-KhL) – Russian analogue of NAYR(Al)Y Cold Resistance АВКаШв-ХЛ (AVKaShv-KhL) – Russian analogue of NAYRY Cold Resistance

VBaShv-KhL, AVBaShv-KhL, VKaShv-KhL, VKShv-KhL, AVKShv-KhL, AVKaShv-KhL, according to specification 16.K121-017-2011

Specifications 16.K121-017-2011

Construction Application area Technical data Calculated data To order
To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

Conductor

Copper or aluminum core of the 1 or 2 class according to GOST 22483.

Insulation

PVC-compound (color coded conductor).

Core arrangement

Insulated conductors of multi-wire conductors twisted in cable core.

Inner sheath

PVC-compound, it is made by extrusion with filling of exterior gaps between insulated cores for no armored neither screened cables.

Cable armoring

In cables of types VKShv-KhL, AVKShv-KhL cable armor is laid with steel, galvanized wires.

In cables of types VBaShv-KhL, AVBaShv-KhL cable armor is laid with two aluminum tapes.

In cables of types VKaShv-KhL and AVKaShvKhL cable armor is laid with aluminum wires.

Cable sheath or jacket

PVC-compound

The cables are designed for transmission and distribution of electric energy in stationary installations on a nominal alternating voltage 0,66 and 1kV, nominal frequency 50 Hz

The cables are used for single installation in cable constructions, open-air electrical installations (cable overpasses, arcades).

The cables armored with steel, galvanized wires or wires of aluminum or aluminum alloy are designed for laying on the route, where the tensile forces during exploration are possible, including for installation in seismically active areas, in conditions of permafrost and areas, subjected to offset soil, in bulk and dry soils.

While manufacturing the cables the materials, which allow the cables to be resistant to low temperatures up to – 600C (degrees below zero) are used.

The class of fire hazard of the cables is according to GOST 31565 01.8.2.5.4.

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, 0C from – 60 to + 50
Minimum bending radius, diameters of cable for multi-core 7,5
for single-core 10
The cables are laid at temperature (without preheat), 0C not below - 15

TABLE 1

Nominal voltage of the cables, number and nominal cross-section of current-carrying conductor

* – for operation in DC voltage only

Type of cable Number of conductors Nominal cross-section of main conductors, mm2
Nominal voltage, kV
0,66 1
VBaShv-KhL, VKaShv-KhL 1 1,5 – 50 1,5 – 1000
AVBaShv-KhL, AVKaShv-KhL 2,5 – 50 2,5 – 1000
VKShv-KhL (1,5 – 1000)*
AVKShv-KhL (2,5 – 1000)*
VKaShv-KhL, VKShv-KhL 2, 3, 4, 5, 6 1,5 – 50 1,5 – 400
AVKShv-KhL, AVKaShv-KhL 2,5 – 50 2,5 - 400