PvVGng(A)-LS PvVGЕng(A)-LS PvBShvng(A)-LS
specifications 16.K71-480-2015
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Conductor
Copper, single-wire or multi-wire of the 1st or 2nd classes according to GOST 22483-2012, of the cross-section for 0.66 kV – 1.5 – 50 mm2;
for 1 kV – 1,5-240 мм2, single-wire – 50-630 мм2;
for 3 kV – 240-630 мм2.
Insulation
Cross-linked, halogen free, polymer composition.
Screen for single-wire cables of nominal voltage 3kV:
It is made of copper tapes or copper wires and a copper tape overlaid spirally.
Core arrangement
Insulated conductors of multi-core cables on 0.66 and 1kV are twisted in a cable core.
The cables have got distinctive markings of insulated cores: color or digital.
Inner sheath or separating layer (for armored cables on voltage 3kV)
It is made by extrusion with filling with the halogen free polymer compositions.
Cable armoring
For cables of types PvBShvng(A)-LS is laid helically with two steel, galvanized tapes.
It is possible to lay the PET-tapes by winding or longitudinally over the armor.
Cable sheath or jacket
PVC-compound of low fire hazard
The cables are designed for transmission and distribution of electric energy in stationary electric installations, for installation in cable structures, buildings and underground structures, including flammable and explosive areas.
The cables of types PvVGEng(A)-LS and PvBShvng(A)-LS of rated voltage 3 kV are used in DC voltage units and they are available in single-core modification.
The class of fire hazard of the cables according to GOST 31565-2012 П1б.8.2.2.2.
Nominal voltage, kV – 0.66, 1 and 3
Ambient temperature during cable operation, 0C - from -50 to +50
Resistant with a relative humidity up to 98% at ambient temperature, degree Celsius: +35
Minimum bending radius, diameters of cable:
for single-wire – 10
for multi-wire – 7.5
Service life, years, not less: 30
Smoke generation in the test cell: not more than 50%
Test category on the flame retardance at group installation in bunches on: А
Equivalent toxicity index, g/m3 , more than: 40
To make an order
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
«*»- required fields