ВБаШвнг(А)-ХЛ (VBAShvng(A)-KhL)– Russian analogue of NYB(Al)Y Cold Resistance Flame Retardant АВБаШвнг(А)-ХЛ (AVBAShvng(A)-KhL)– Russian analogue of NAYB(Al)Y Cold Resistance Flame Retardant ВКШвнг(А)-ХЛ (VKShvng(A)-KhL)– Russian analogue of NYRY Cold Resistance Flame Retardant АВКШвнг(А)-ХЛ (AVKShvng(A)-KhL)– Russian analogue of NAYRY Cold Resistance Flame Retardant ВКаШвнг(А)-ХЛ (VKaShvng(A)-KhL)– Russian analogue of NYR(Al)Y Cold Resistance Flame Retardant АВКаШвнг(А)-ХЛ (AVKaShvng(A)-KhL)– Russian analogue of NAYR(Al)Y Cold Resistance Flame Retardant
specifications 16.K121-017-2011
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Conductor
Copper or aluminum core of circular of sector-shaped form, of the 1 or 2 class according to GOST 22483.
Insulation
PVC-compound (color coded conductor)
Core arrangement
Insulated conductors of multi-core cables are twisted It is allowed to manufacture cables with SZ-stranding.
Inner sheath
PVC-compound or PVC-compound of low flammability is manufactured with the filling of exterior gaps between insolated conductors.
Cable armoring
For cables of types VBAShvng(A)-KhL and AVBAShvng(A)-KhL is laid with aluminum tapes.
For cables of types VKaShvng(A)-KhL, AVKaShvng(A)-KhL is laid with aluminum wires.
For cables of types VKShvng(A)-KhL, AVKShvng(A)-KhL is laid with steel, galvanized wires.
Cable sheath or jacket
PVC-compound of low flammability
The cables are designed for transmission and distribution of electric energy in stationary electric installations on alternating voltage 0,66 and 1 kV and frequency 50 Hz.
The cables are used for group installation in cable constructions, open-air electrical installations (cable overpasses, arcades).
The cables armored with steel, galvanized wires or wires of aluminum or aluminum alloy are designed for laying on the route, where the tensile forces during exploration are possible, including for installation in seismically active areas, in conditions of permafrost and areas, subjected to offset soil, in bulk and dry soils.
While manufacturing the cables the materials, which allow the cables to be resistant to low temperatures up to – 600C (degrees below zero) are used.
The class of fire hazard of the cables according to GOST 31565 П1б.8.2.5.4.
Nominal voltage, kV | 0,66 or 1 | |
Ambient temperature during cable operation, °С | from – 60 to + 50 | |
Minimum bending radius, diameters of cable | for multi-wire | 7,5 |
for single-wire | 10 | |
The cables are laid at temperature (without preheat), °С, not below | - 15 |
TABLE 1
Nominal voltage of the cables, number and nominal cross-section of current-carrying conductor
* – for operation in DC voltage only
Type of cable | Number of conductors | Nominal cross-section of main conductors, mm2 | |
Nominal voltage, kV | |||
0,66 | 1 | ||
VBaShvng (A)-KhL, VKaShvng (A)-KhL | 1 | 1,5 - 50 | 1,5 - 1000 |
AVBaShvng (A)-KhL, AVKaShvng (A)-KhL | 2,5 - 50 | 2,5 - 1000 | |
VKShvng (A)-KhL | – | (1,5 - 1000)* | |
AVKShvng (A)-KhL | – | (2,5 - 1000)* | |
VKShvng (A)-KhL, VKaShvng (A)-KhL | 2, 3, 4, 5, 6 | 1,5 - 50 | 1,5 - 400 |
AVKShvng (A)-KhL, AVKaShvng (A)-KhL | 2,5 - 50 | 2,5 - 400 |