ВВГ-Пнг(А)-FRLSLTx (VVG-Png(A)-FRLSLTx) – Russian analogue of NYBY Fire Resistance Low Smoke Low Toxicity FE180 MICA

ВВГ-Пнг(А)-FRLSLTx (VVG-Png(A)-FRLSLTx) – Russian analogue of NYBY Fire Resistance Low Smoke Low Toxicity FE180 MICA

Description Add to order

SCOPE AND PURPOSE

The cables are designed for transmission and distribution of electric power in stationary installations on the nominal alternating voltage to 0.66 and 1kV and frequency 50 Hz. The cables are used at group installation; they do not spread combustion on category A.

The cables are designed for group installation of cable power supply lines of electrical equipment of safety systems, (the wiring circuits of systems of fire alarm, power of pumps of fire suppression. Illuminations of emergency exits and escape routes, smoke removal systems and ventilation, evacuation lifts),including residential and public buildings, in buildings of children’s preschool educational institutions, retirement and nursing homes, hospitals, the dormitories of educational establishments of boarding schools, hotels, dormitories, of the dormitories sanatoriums and vacation houses of general type, motels, resorts and spectacular clubs, sports facilities, buildings of the organization for the maintenance of the population, of subways, in case of absence of danger of mechanical damages of the cables. For wiring in the surgical departments of hospitals, of the wiring circuits of emergency power supply of the equipment (current collectors), functioning in case of fire. They keep working in case of fire during 180 (FE180) or 240 (FE240) minutes.

The class of fire hazard of the cables according to GOST 31565-2012 for cables П1б.1.2.1.2.

STRUCTURE

Conductor

Copper, single-wire or multi-wire core, of round or sector-shaped form, of the 1 or 2 class according to GOST 22483.

Thermal barrier for CCC (current-carrying conductor)(For FE180 and FE240)

The overlapping with two mica tapes.

Insulation(color coded conductor)

Made of low toxicity PVC-compound of low fire hazard.

Core arrangement and twisting

2 or 3 insulated cores are situated in parallel in one flat.

Inner sheath

Made of low toxicity PVC-compound of low fire hazard.

Thermal barrier on the inner sheath (For FE240)

Overlapping with the fiber glass and mica tapes.

Over sheath or jacket

Made of low toxicity PVC-compound of low fire hazard

Number of conductors, nominal cross-section (mm2), construction, voltage (kV) Calculated diameter of cable, mm Calculated weight of cable, kg/km
height width
VVG-Png(A)-FRLSLTx 2х1,5ок(N)-0,66 6,6 10,3 119
m
VVG-Png(A)-FRLSLTx 2х2,5ок(N)-0,66 7 11,1 144
m
VVG-Png(A)-FRLSLTx 2х4ок(N)-0,66 7,6 12,5 190
m
VVG-Png(A)-FRLSLTx 2х6ок(N)-0,66 8,1 13,4 236
m
VVG-Png(A)-FRLSLTx 2х10ок(N)-0,66 9,5 16 410
m
VVG-Png(A)-FRLSLTx 2х16ок(N)-0,66 10,4 17,8 566
m
VVG-Png(A)-FRLSLTx 3х1,5ок(N,PE)-0,66 6,6 14,1 170
m
VVG-Png(A)-FRLSLTx 3х2,5ок(N,PE)-0,66 7 15,3 268
m
VVG-Png(A)-FRLSLTx 3х4ок(N,PE)-0,66 7,6 17,3 277
m
VVG-Png(A)-FRLSLTx 3х6ок(N,PE)-0,66 8,1 18,8 346
m
VVG-Png(A)-FRLSLTx 3х10ок(N,PE)-0,66 9,5 22,6 606
m
VVG-Png(A)-FRLSLTx 3х16ок(N,PE)-0,66 10,4 25,3 842
m
VVG-Png(A)-FRLSLTx 2х1,5ок(N)-1 7 11,1 139
m
VVG-Png(A)-FRLSLTx 2х2,5ок(N)-1 7,4 11,9 166
m
VVG-Png(A)-FRLSLTx 2х4ок(N)-1 8,2 13,7 223
m
VVG-Png(A)-FRLSLTx 2х6ок(N)-1 8,7 14,6 272
m
VVG-Png(A)-FRLSLTx 2х10ок(N)-1 9,7 16,4 431
m
VVG-Png(A)-FRLSLTx 2х16ок(N)-1 10,6 18,2 590
m
VVG-Png(A)-FRLSLTx 3х1,5ок(N,PE)-1 7 15,3 192
m
VVG-Png(A)-FRLSLTx 3х2,5ок(N,PE)-1 7,4 16,5 231
m
VVG-Png(A)-FRLSLTx 3х4ок(N,PE)-1 8,2 19,1 315
m
VVG-Png(A)-FRLSLTx 3х6ок(N,PE)-1 8,7 20,6 387
m
VVG-Png(A)-FRLSLTx 3х10ок(N,PE)-1 9,7 23,2 622
m
VVG-Png(A)-FRLSLTx 3х16ок(N,PE)-1 10,6 25,9 859
m