РВГнг(А)-FRLSTx (RVGng(A)-FRLSTx) – Russian analogue of NHXMY Fire Resistance Low Smoke Low Toxicity FE180/E30 KERAM РВГ-Пнг(А)-FRLSTx (RVG-Png(A)-FRLSTx) – Russian analogue of NHXIFMY Fire Resistance Low Smoke Low Toxicity FE180/E30 KERAM РВГЭнг(А)-FRLSTx (RVGEng(A)-FRLSTx) – Russian analogue of NHXCMY Fire Resistance Low Smoke Low Toxicity FE180/E30 KERAM

RVGng(A)-FRLSTx, RVG-Png(A)-FRLSTx, RVGEng(A)-FRLSTx, according to specifications 16.K121-026-2013

specifications 16.K121-026-2013

Construction Application area Technical data To order
To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

Conductor

Copper of round form, single-wire with the cross-section from 1.5 to 16 mm2 of the 1 class or multi-wire core with the cross-section from 10 to 16 mm2 of the 2 class according to GOST 22483.

From 1 to 5 conductors.

Insulation

Ceramic forming silicone rubber.

Core arrangement

Insulated conductors of 2-5 core cables are twisted.

Insulated conductors of 2 and 3 core cables of types RVG-Png(A)-FRLSTx are arranged in parallel in one flat.

Inner sheath

PVC-compound of low toxicity.

Screen

For cables of types RVGEng(A)-FRLSTx is made of copper tapes.

Over sheath

PVC-compound of low toxicity

The cables are designed for transmission and distribution of electric power in stationary installations on the nominal alternating voltage to 0.66 and 1kV and frequency 50 Hz.

The cables do not spread combustion at group installation of cable lines in the absence of mechanical effects on the cable and keep working when exposed by flame on the cable not less than 180 minutes.

The cables are designed for wiring and emergency power circuits of equipment (current collectors), in residential and public buildings, in the surgical departments of hospitals, in the office premises, equipped with computer and micro processor devices, spectacular complexes and sports facilities, as well as in other objects with the high demand of fire safety.

The class of fire hazard of the cables according to GOST 31565 П1б.1.2.1.2.

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, °С from – 40 to + 50
Minimum bending radius, diameters of cable for multi-wire 7,5
for single-wire 10
Durable permissible temperature of heating cables lived during operation, °C, not more than 95
Equivalent toxicity of combustion products of the cable product, g/m2, not more than 120
The cables are laid at temperature (without preheat), °С, not below - 15
The service life of the cable, years 40