ПвБШвнг(А)-FRLS – (PvBShvng(A)-FRLS) – Russian analogue of NHXBYu Fire Resistance Low Smoke FE180 MICA

PvBShvng(A)-FRLS

Description Add to order

 

SCOPE AND PURPOSE

The cables are designed for transmission and distribution of electric energy in stationary electric installations, for installation in cable structures, buildings and underground structures, including flammable and explosive areas, for supply chains of the equipment, which operates in fire.

The cables of types PvPGEng(A)-FRLS and PvBPng(A)- FRLS of rated voltage 3 kV are used in DC voltage units and they are available in single-core modification.

The class of fire hazard of the cables according to GOST 31565-2012 П1б.1.2.2.2.

 

TECHNICAL DATA

Nominal voltage, kV – 0.66, 1 or 3

Ambient temperature during cable operation, 0C - from -50 to +50

Resistant with a relative humidity up to 98% at ambient temperature, degree Celsius, up to +35

Minimum bending radius, diameters of cable:

for single-wire – 10

for multi-wire – 7.5

Service life, years, not less: 30

Flame retardant at group installation in bunches on category: А

Equivalent toxicity index, g/m3 , more than: 40

Fire resistance of the cable, minutes, not less than: 180

 

STRUCTURE

Conductor

Copper, single-wire or multi-wire of the 1st or 2nd classes according to GOST 22483-2012, of the cross-section for 0.66 kV – 1.5 – 50 mm2 ;

for 1 kV – 1.5 – 240 mm2, single-wire – 50-630 мм2;

for 3 kV – 240 – 360 mm2.

Thermal barrier

The lapping with mica tapes.

Insulation

Cross-linked, halogen free, polymer composition.

Screen for single-wire cables of nominal voltage 3kV:

It is made of copper tapes or copper wires and a copper tape overlaid spirally.

Core arrangement

Insulated conductors of multi-core cables on 0.66 and 1kV are twisted in a cable core.

The cables have got distinctive markings of insulated cores: color or digital.

Inner sheath or separating layer (for armored cables on voltage 3kV)

It is made by extrusion with filling with the halogen free polymer compositions.

Cable armoring

For cables of types PvBShvng(A)-FRLS is laid helically with two steel, galvanized tapes.

It is possible to lay the PET-tapes by winding or longitudinally over the armor.

Cable sheath or jacket

PVC-compound of low fire hazard.

Number and nominal cross-section of conductors (mm2) External diameter of cable, mm Weight, kg
PvBShvng(A)-FRLS 3х1,5-0,66 14,8 404
km
PvBShvng(A)-FRLS 3х2,5-0,66 15,6 468
km
PvBShvng(A)-FRLS 3х4-0,66 16,6 552
km
PvBShvng(A)-FRLS 3х6-0,66 17,7 654
km
PvBShvng(A)-FRLS 3х10-0,66 19,5 841
km
PvBShvng(A)-FRLS 3х16-0,66  21,5 1100
km
PvBShvng(A)-FRLS 3х25-0,66  26,7 1650
km
PvBShvng(A)-FRLS 3х35-0,66  29,4 2081
km
PvBShvng(A)-FRLS 3х50-0,66  28,7 3970
km
PvBShvng(A)-FRLS 4х1,5-0,66 15,7 450
km
PvBShvng(A)-FRLS 4х2,5-0,66 16,7 527
km
PvBShvng(A)-FRLS 4х4-0,66 17,8 629
km
PvBShvng(A)-FRLS 4х6-0,66 19,1 754
km
PvBShvng(A)-FRLS 4х10-0,66 21 984
km
PvBShvng(A)-FRLS 4х16-0,66  23,3 1305
km
PvBShvng(A)-FRLS 4х25-0,66  29,3 1983
km
PvBShvng(A)-FRLS 4х35-0,66  32 2499
km
PvBShvng(A)-FRLS 4х50-0,66  31,7 5114
km
PvBShvng(A)-FRLS 5х1,5-0,66 16,8 494
km
PvBShvng(A)-FRLS 5х2,5-0,66 17,9 582
km
PvBShvng(A)-FRLS 5х4-0,66 19,2 701
km
PvBShvng(A)-FRLS 5х6-0,66 20,5 847
km
PvBShvng(A)-FRLS 5х10-0,66 22,7 1116
km
PvBShvng(A)-FRLS 5х16-0,66 25,7 1522
km
PvBShvng(A)-FRLS 5х25-0,66  31,9 2267
km
PvBShvng(A)-FRLS 5х35-0,66  35,6 2937
km
PvBShvng(A)-FRLS 5х50-0,66 35,4 6334
km
Number and nominal cross-section of conductors (mm2) External diameter of cable, mm Weight, kg
PvBShvng(A)-FRLS 1х50-1 18,8 919
km
PvBShvng(A)-FRLS 1х70-1 19,8 1135
km
PvBShvng(A)-FRLS 1х95-1 21,4 1414
km
PvBShvng(A)-FRLS 1х120-1 23,1 1704
km
PvBShvng(A)-FRLS 1х150-1 25,5 2087
km
PvBShvng(A)-FRLS 1х185-1 27,5 2490
km
PvBShvng(A)-FRLS 1х240-1 30,2 3101
km
PvBShvng(A)-FRLS 1х300-1 32,9 3784
km
PvBShvng(A)-FRLS 1х400-1 37,5 5093
km
PvBShvng(A)-FRLS 1х500-1 40,9 6195
km
PvBShvng(A)-FRLS 1х625/630-1 45,1 7658
km
PvBShvng(A)-FRLS 3х1,5-1 15,2 423
km
PvBShvng(A)-FRLS 3х2,5-1 16,1 487
km
PvBShvng(A)-FRLS 3х4-1 17,1 573
km
PvBShvng(A)-FRLS 3х6-1 18,2 676
km
PvBShvng(A)-FRLS 3х10-1 19,9 864
km
PvBShvng(A)-FRLS 3х16-1  21,9 1125
km
PvBShvng(A)-FRLS 3х25-1  27,2 1679
km
PvBShvng(A)-FRLS 3х35-1  29,8 2111
km
PvBShvng(A)-FRLS 3х50-1 28,5 2273
km
PvBShvng(A)-FRLS 3х70-1 31,6 2967
km
PvBShvng(A)-FRLS 3х95-1 34,5 3813
km
PvBShvng(A)-FRLS 3х120-1 38,1 4863
km
PvBShvng(A)-FRLS 3х150-1 41,6 5927
km
PvBShvng(A)-FRLS 3х185-1 45,8 7213
km
PvBShvng(A)-FRLS 3х240-1 50,1 8984
km
PvBShvng(A)-FRLS 4х1,5-1 16,2 471
km
PvBShvng(A)-FRLS 4х2,5-1 17,2 548
km
PvBShvng(A)-FRLS 4х4-1 18,3 652
km
PvBShvng(A)-FRLS 4х6-1 19,5 778
km
PvBShvng(A)-FRLS 4х10-1 21,5 1010
km
PvBShvng(A)-FRLS 4х16-1  24,2 1359
km
PvBShvng(A)-FRLS 4х25-1 29,8 2014
km
PvBShvng(A)-FRLS 4х35-1  32,9 2573
km
PvBShvng(A)-FRLS 4х50-1  31,5 2888
km
PvBShvng(A)-FRLS 4х70-1 35,6 3851
km
PvBShvng(A)-FRLS 4х95-1 39,8 5169
km
PvBShvng(A)-FRLS 4х120-1 43 6278
km
PvBShvng(A)-FRLS 4х150-1 47,5 7731
km
PvBShvng(A)-FRLS 4х185-1 51,6 9313
km
PvBShvng(A)-FRLS 4х240-1 57,4 11789
km
PvBShvng(A)-FRLS 5х1,5-1 17,3 517
km
PvBShvng(A)-FRLS 5х2,5-1 18,4 606
km
PvBShvng(A)-FRLS 5х4-1 19,7 725
km
PvBShvng(A)-FRLS 5х6-1 21,1 872
km
PvBShvng(A)-FRLS 5х10-1 23,2 1143
km
PvBShvng(A)-FRLS 5х16-1 26,2 1551
km
PvBShvng(A)-FRLS 5х25-1  32,9 2339
km
PvBShvng(A)-FRLS 5х35-1  36,9 3190
km
PvBShvng(A)-FRLS 5х50-1 35,2 3559
km
PvBShvng(A)-FRLS 5х70-1 40 4935
km
PvBShvng(A)-FRLS 5х95-1 43,8 6278
km
PvBShvng(A)-FRLS 5х120-1 48 7737
km
PvBShvng(A)-FRLS 5х150-1 52,4 9439
km
PvBShvng(A)-FRLS 5х185-1 57,9 11537
km
PvBShvng(A)-FRLS 5х240-1 63,6 14453
km
Number and nominal cross-section of conductors (mm2) External diameter of cable, mm Weight, kg
PvBShvng(A)-FRLS 1х240-3 36,4 3397
km
PvBShvng(A)-FRLS 1х300-3 38,7 4042
km
PvBShvng(A)-FRLS 1х400-3 42,1 5115
km
PvBShvng(A)-FRLS 1х500-3 46,5 6452
km
PvBShvng(A)-FRLS 1х630-3 51,1 7963
km