ВВГнг(А)-FRLS (VVGng(A)-FRLS)– Russian analogue of NYY Fire Resistance Low Smoke FE180 MICA ВВГЭнг(А)-FRLS (VVGЕng(A)-FRLS)– Russian analogue of NYCY, NYCWY Fire Resistance Low Smoke FE180 MICA

VVGng(A)-FRLS, VVGЕng(A)-FRLS, according to specifications 16.K71-337-2004

specifications 16.K71-337-2004

Construction Application area Technical data To order
To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

Conductor

Copper, single-wire or multi-wire core, of circular or sector-shaped form, of the 1 or 2 class according to GOST 22483.

Insulation

XLPE (color coded conductor).

Core arrangement

Insulated conductors of multi-wire cables are twisted on a cable core.

Inner sheath

It’s made with the filling of exterior gaps between the conductors of halogen-free polymer composition.

Lapping

For cables with the conductors of cross-section 50mm2 and more is made of one fiber glass tape.

Screen

For cables of types VVGЕng(A)-FRLS the screen is made in form of lapping with copper tapes or by agreement with the customer with copper wires and a spiral taping with a copper tape.

Cable sheath

It’s made of halogen-free polymer composition.

ВВГнг(А)-FRLS 3х1,5
ВВГнг(А)-FRLS 1х120
ВВГнг(А)-FRLS 1х150
ВВГнг(А)-FRLS 1х240
ВВГнг(А)-FRLS 1х25
ВВГнг(А)-FRLS 1х35
ВВГнг(А)-FRLS 1х95
ВВГнг(А)-FRLS 1х50
ВВГнг(А)-FRLS 5х120
ВВГнг(А)-FRLS 5х150
ВВГнг(А)-FRLS 5х25
ВВГнг(А)-FRLS 5х35
ВВГнг(А)-FRLS 5х70
ВВГнг(А)-FRLS 5х95

The cables are designed for transmission and distribution of electric power and electrical signal in stationary electrical installations on the nominal alternating voltage to 0.66 and 1kV and frequency 50 Hz or on direct voltage 1 and 1.5 kV.

The cables are designed for group installations of cable power supply lines use in security systems of nuclear power stations of classes 2 and 3 according to classification of ОПБ 88/97 (ПНАЭ Г-01-011).

The climate modification B, the category of location 5, according to GOST 15150-69

The class of fire hazard of the cables according to GOST 31565 П1Б.8.1.2.1.

Nominal voltage, kV 0,66 or 1
Ambient temperature during cable operation, °С from – 50 to + 50
Minimum bending radius, diameters of cable for multi-wire 7,5
for single-wire 10
The cables are laid at temperature (without preheat), °С, not below - 15
Fire resistance of the cables, min, not less 180
Smoke emission in the test cell not more than 50%

To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

«*»- required fields