КВВГнг(А)-FRLS (KVVGng(A)-FRLS) - Russian analogue of NYY Low Smoke FE180/E60 MICA КВВГЭнг(А)-FRLS (KVVGЕng(A)-FRLS) - Russian analogue of NYСY Low Smoke FE180/E60 MICA

KVVGng(A)-FRLS, KVVGЕng(A)-FRLS, according to specifications 16.K71-337-2004

specifications 16.K71-337-2004

Construction Application area Technical data To order
To make an order

You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.

Conductor

Copper, single-wire, of the 1 class according to GOST 22483, with the cross-section from 0.75 to 6 mm2.

Thermal barrier

The lapping with two mica tapes.

Core arrangement

Number of conductors from 4 to 61.

The insulated conductors are twisted in the cable core, the conductors are color-coded, which provide the identification of each core during installation.

Color-coded is solid or in the form of longitudinal strips of a width not less than 1mm.

Inner sheath

For cables of types KVVGЕng(A)-FRLS –PVC-compound of low fire hazard.

Screen

For cables of types KVVGЕng(A)-FRLS is made in the form of taping with copper wire or copper foil.

Over sheath

PVC-compound of low fire hazard.

The cables are designed for fixed connection to electrical devices and equipment, to assemblies of clamps of electrical switch gear with the nominal alternating voltage up to 660V of frequency up to 100 Hz or direct voltage up to 1000V, for group installation with taking into account the volume of combustible load of the cables in the fire protection systems and other systems that must remain operational in case of fire within 180 minutes.

The screened cables are used when it is necessary to protect the electrical circuits from the influence of external electric fields.

The cables are manufactured for general industrial use and use in nuclear power stations (NPP) outside the hermetical unit in the system as class 2 according to the classification ОПБ 88/97 (ПНАЭ Г-01-11)

The class of fire hazard of the cables according to GOST 31565 П1б.1.2.2.2.

Nominal voltage, kV up to 0,66
Ambient temperature during cable operation, °С from – 50 to + 50
Minimum bending radius of the cables, diameters of the cable 6
The ambient temperature for installation of the cables (without preheat), °С, not below - 15
Fire resistant of the cables, min, not less 180
Smoke generation in the test cell not more than 50%
Warranty period 5 years