КППГЭнг(А)-FRHF (KPPGЕng(A)-FRHF) - Russian analogue of NHXCH FE180/E90 MICA
SCOPE AND PURPOSE
The cables are designed for fixed connection to electrical devices and equipment, to assemblies of clamps of electrical switch gear with the nominal alternating voltage up to 660V of frequency up to 100 Hz or direct voltage up to 1000V, the cables are used at group installation of cable lines of power and control circuits.
The cables are used at group installation of cable lines of power and control circuits.
The cables are designed for use at large thermal power stations, petrochemical objects, in the subway, in buildings and structures with mass stay of people, concert halls and indoor stadiums, theatres, airports and railway stations; in premises, equipped with computer and microprocessor appliances and other objects which have increased requirements for fire safety.
The cable keeps working in case of fire during 180 minutes.
The screened cables are used when it is necessary to protect the electrical circuits from the influence of external electric fields.
The class of fire hazard of the cables according to GOST 31565 of cables of modification “flame retardant (A) - Fire Resistant Halogen Free”- П1б.1.1.2.1.
STRUCTURE
Conductor
Copper, single-wire, of the 1 class according to GOST 22483, with the cross-section from 0.75 to 6 mm2.
Thermal barrier
The lapping with fiber-glass mica tapes.
Insulation
Halogen free polymer composition.
Core arrangement and twisting
From 4 to 127 insulated conductors.
The insulated conductors are twisted; there is a marker pair in each layer.
It is allowed digital and color coded marking of the conductors.
Separating layer
Halogen-free polymer composition.
Screen
For cables of types KPPGЕng(A)-FRHF taping with a copper tape.
Cable sheath or jacket
Halogen free polymer composition.
Number of conductors, nominal cross-section (mm2), construction, voltage (kV) | Calculated diameter of cable, mm | Calculated weight of cable, kg/km | |
KPPGЕng(A)-FRHF 4х0,75 FE180/E90 | 13,0 | 233 | |
KPPGЕng(A)-FRHF 5х0,75 FE180/E90 | 13,9 | 271 | |
KPPGЕng(A)-FRHF 7х0,75 FE180/E90 | 14,9 | 320 | |
KPPGЕng(A)-FRHF 10х0,75 FE180/E90 | 18,6 | 446 | |
KPPGЕng(A)-FRHF 14х0,75 FE180/E90 | 20,0 | 545 | |
KPPGЕng(A)-FRHF 19х0,75 FE180/E90 | 21,9 | 672 | |
KPPGЕng(A)-FRHF 27х0,75 FE180/E90 | 26,1 | 914 | |
KPPGЕng(A)-FRHF 37х0,75 FE180/E90 | 28,9 | 1154 | |
KPPGЕng(A)-FRHF 52х0,75 FE180/E90 | 33,6 | 1534 | |
KPPGЕng(A)-FRHF 4х1,0 FE180/E90 | 13,3 | 251 | |
KPPGЕng(A)-FRHF 5х1,0 FE180/E90 | 14,3 | 293 | |
KPPGЕng(A)-FRHF 7х1,0 FE180/E90 | 15,4 | 349 | |
KPPGЕng(A)-FRHF 10х1,0 FE180/E90 | 19,2 | 487 | |
KPPGЕng(A)-FRHF 14х1,0 FE180/E90 | 20,6 | 599 | |
KPPGЕng(A)-FRHF 19х1,0 FE180/E90 | 22,7 | 744 | |
KPPGЕng(A)-FRHF 27х1,0 FE180/E90 | 27,0 | 1014 | |
KPPGЕng(A)-FRHF 37х1,0 FE180/E90 | 30,0 | 1287 | |
KPPGЕng(A)-FRHF 52х1,0 FE180/E90 | 35,2 | 1754 | |
KPPGЕng(A)-FRHF 4х1,5 FE180/E90 | 13,9 | 281 | |
KPPGЕng(A)-FRHF 5х1,5 FE180/E90 | 14,9 | 333 | |
KPPGЕng(A)-FRHF 7х1,5 FE180/E90 | 16,0 | 397 | |
KPPGЕng(A)-FRHF 10х1,5 FE180/E90 | 20,1 | 557 | |
KPPGЕng(A)-FRHF 14х1,5 FE180/E90 | 21,6 | 693 | |
KPPGЕng(A)-FRHF 19х1,5 FE180/E90 | 24,2 | 890 | |
KPPGЕng(A)-FRHF 27х1,5 FE180/E90 | 28,4 | 1187 | |
KPPGЕng(A)-FRHF 37х1,5 FE180/E90 | 31,6 | 1518 | |
KPPGЕng(A)-FRHF 4х2,5 FE180/E90 | 14,8 | 337 | |
KPPGЕng(A)-FRHF 5х2,5 FE180/E90 | 16,0 | 400 | |
KPPGЕng(A)-FRHF 7х2,5 FE180/E90 | 17,2 | 487 | |
KPPGЕng(A)-FRHF 10х2,5 FE180/E90 | 21,6 | 686 | |
KPPGЕng(A)-FRHF 14х2,5 FE180/E90 | 23,7 | 888 | |
KPPGЕng(A)-FRHF 19х2,5 FE180/E90 | 26,1 | 1121 | |
KPPGЕng(A)-FRHF 27х2,5 FE180/E90 | 30,8 | 1509 | |
KPPGЕng(A)-FRHF 37х2,5 FE180/E90 | 34,6 | 1985 | |
KPPGЕng(A)-FRHF 4х4 FE180/E90 | 16,4 | 432 | |
KPPGЕng(A)-FRHF 5х4 FE180/E90 | 17,8 | 519 | |
KPPGЕng(A)-FRHF 7х4 FE180/E90 | 19,6 | 664 | |
KPPGЕng(A)-FRHF 10х4 FE180/E90 | 24,7 | 932 | |
KPPGЕng(A)-FRHF 4х6 FE180/E90 | 17,6 | 530 | |
KPPGЕng(A)-FRHF 5х6 FE180/E90 | 19,5 | 664 | |
KPPGЕng(A)-FRHF 7х6 FE180/E90 | 21,1 | 826 | |
KPPGЕng(A)-FRHF 10х6 FE180/E90 | 26,7 | 1167 |