Conductor

Copper, single-wire, of the 1 class according to GOST 22483, with the cross-section from 0.75 to 6 mm2.

Thermal barrier

The lapping with fiber-glass mica tapes.

Insulation

Halogen free polymer composition.

Core arrangement and twisting

From 4 to 127 insulated conductors.

The insulated conductors are twisted; there is a marker pair in each layer.

It is allowed digital and color coded marking of the conductors.

Separating layer

Halogen-free polymer composition.

Screen

For cables of types KPPGЕng(A)-FRHF taping with a copper tape.

Cable armoring

For cables of types KPBbPng(A)-FRHF is laid helically with two steel, galvanized tapes.

Cable sheath or jacket

Halogen free polymer composition.

The cables are designed for fixed connection to electrical devices and equipment, to assemblies of clamps of electrical switch gear with the nominal alternating voltage up to 660V of frequency up to 100 Hz or direct voltage up to 1000V, the cables are used at group installation of cable lines of power and control circuits.

The cables are used at group installation of cable lines of power and control circuits.

The cables are designed for use at large thermal power stations, petrochemical objects, in the subway, in buildings and structures with mass stay of people, concert halls and indoor stadiums, theatres, airports and railway stations; in premises, equipped with computer and microprocessor appliances and other objects which have increased requirements for fire safety.

The cable keeps working in case of fire during 180 minutes.

The screened cables are used when it is necessary to protect the electrical circuits from the influence of external electric fields.

The armored cables are used in case of danger of mechanic damage in process of operation, if the cable is not exposed to significant tensile force.

The class of fire hazard of the cables according to GOST 31565 of cables of modification “flame retardant (A) - Fire Resistant Halogen Free”- П1б.1.1.2.1.

Nominal voltage, kV 0.66
Ambient temperature during cable operation , °С from – 50 to + 50
Durably allowable temperature of heating of conductors during operation, °С + 70
Minimum bending radius of the cables at laying and installation, diameters of the cable armored 10
non-armored 6
The ambient temperature for installation of the cables (without preheat), °С, not below - 15