КВВГЭнг(А)- FRLSLTx - (KVVGЕng(A)- FRLSLTx) - Russian analogue of NYSYu Fire Resistance Low Smoke Low Toxicity FE180 MICA

KVVGЕng(A)- FRLSLTx

Description Add to order

SCOPE AND PURPOSE

The cables are designed for fixed connection to electrical devices and equipment, to assemblies of clamps of electrical switch gear with the nominal alternating voltage up to 660V of frequency up to 100 Hz or direct voltage up to 1000V, for group installation with taking into account the volume of combustible load of the cables in buildings, in fire protection systems, fire alarm systems, warning and evacuation in case of fire in buildings, construction and structures with mass stay of people (industrial plants, schools, hospitals, office buildings, railway stations and so on). The screened cables are used when it is necessary to protect the electrical circuits from the influence of external electric fields. The armored cables are used in case of danger of mechanic damage in process of operation, if the cable is not exposed to significant tensile force

The class of fire hazard of the cables according to GOST 31565 П1б.1.2.1.2

 

TECHNICAL DATA

Nominal voltage, kV : 0,66

Ambient temperature during cable operation, °С: from -50 to +50

Durably allowable temperature of heating of conductors during operation, °С: +70

Minimum bending radius of the cables at installation, diameters of the cable: armored 10, non-armored 6

The ambient temperature for installation of the cables (without preheat), °С, not below: -15

Smoke generation in the test cell: not more than 50 %

Fire resistance of the cable, minutes, not less than: 180

Service life, years, not less: 30

The cables do not spread combustion at group installation on category: А

Equivalent toxicity index, g/m3 , more than: 120

 

STRUCTURE

Conductor

Copper, single-wire, of the 1 class according to GOST 22483, with the cross-section from 0.75 to 6 mm2.

Thermal barrier

Mica tape winding.

Insulation

Low toxic PVC-compound of low fire hazard.

Core arrangement

КThe number of conductors from 4 to 127. The insulated conductors are twisted; there is a marker pair in each layer. It is allowed digital and color coded marking of the conductors.

Separating layer

Low toxic PVC-compound of low fire hazard.

Screen

For cables of types KVVGЕng(A)- FRLSLTx is made as a helically overlapping superimposed with copper tapes.

Cable armoring

For cables of types KVBbShvng(A)- FRLSLTx is laid helically with two steel, galvanized tapes.

Cable sheath or jacket

Low toxic PVC-compound of low fire hazard.

Number and nominal cross-section of conductors (mm2) External diameter of cable, mm Weight, kg
KVVGЕng(A)- FRLSLTx 4х0,75  12,7 249
km
KVVGЕng(A)- FRLSLTx 5х0,75  13,6 288
km
KVVGЕng(A)- FRLSLTx 7х0,75  14,5 335
km
KVVGЕng(A)- FRLSLTx 10х0,75 17,6 444
km
KVVGЕng(A)- FRLSLTx 14х0,75 19,3 560
km
KVVGЕng(A)- FRLSLTx 19х0,75  21,1 683
km
KVVGЕng(A)- FRLSLTx 27х0,75  25,1 922
km
KVVGЕng(A)- FRLSLTx 37х0,75  27,7 1155
km
KVVGЕng(A)- FRLSLTx 52х0,75 32,1 1512
km
KVVGЕng(A)- FRLSLTx 4х1,0  13 266
km
KVVGЕng(A)- FRLSLTx 5х1,0 14 310
km
KVVGЕng(A)- FRLSLTx 7х1,0  15 364
km
KVVGЕng(A)- FRLSLTx 10х1,0 18,6 505
km
KVVGЕng(A)- FRLSLTx 14х1,0  19,9 614
km
KVVGЕng(A)- FRLSLTx 19х1,0  21,9 755
km
KVVGЕng(A)- FRLSLTx 27х1,0 26 1022
km
KVVGЕng(A)- FRLSLTx 37х1,0 28,8 1287
km
KVVGЕng(A)- FRLSLTx 52х1,0 33,3 1693
km
KVVGЕng(A)- FRLSLTx 4х1,5 13,6 297
km
KVVGЕng(A)- FRLSLTx 5х1,5  14,6 351
km
KVVGЕng(A)- FRLSLTx 7х1,5 15,6 413
km
KVVGЕng(A)- FRLSLTx 10х1,5 19,5 575
km
KVVGЕng(A)- FRLSLTx 14х1,5  21 706
km
KVVGЕng(A)- FRLSLTx 19х1,5 23 877
km
KVVGЕng(A)- FRLSLTx 27х1,5 27,4 1191
km
KVVGЕng(A)- FRLSLTx 37х1,5  30,4 1512
km
KVVGЕng(A)- FRLSLTx 4х2,5  14,5 355
km
KVVGЕng(A)- FRLSLTx 5х2,5  15,6 420
km
KVVGЕng(A)- FRLSLTx 7х2,5  16,8 504
km
KVVGЕng(A)- FRLSLTx 10х2,5  21 706
km
KVVGЕng(A)- FRLSLTx 14х2,5 22,6 881
km
KVVGЕng(A)- FRLSLTx 19х2,5  25,3 1135
km
KVVGЕng(A)- FRLSLTx 27х2,5  29,7 1517
km
KVVGЕng(A)- FRLSLTx 37х2,5  33 1948
km
KVVGЕng(A)- FRLSLTx 4х4  16,1 455
km
KVVGЕng(A)- FRLSLTx 5х4 17,4 545
km
KVVGЕng(A)- FRLSLTx 7х4  19,2 686
km
KVVGЕng(A)- FRLSLTx 10х4  24,1 963
km
KVVGЕng(A)- FRLSLTx 4х6  17,3 555
km
KVVGЕng(A)- FRLSLTx 5х6 19,2 694
km
KVVGЕng(A)- FRLSLTx 7х6 20,7 853
km
KVVGЕng(A)- FRLSLTx 10х6  26,1 1200
km