KVVGng(A)- FRLSLTx KVVGЕng(A)- FRLSLTx KVBbShvng(A)- FRLSLTx
Specification 3563-010-53972660-2010
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Conductor
Copper, single-wire, of the 1 class according to GOST 22483, with the cross-section from 0.75 to 6 mm2.
Thermal barrier
Mica tape winding.
Insulation
Low toxic PVC-compound of low fire hazard.
Core arrangement
КThe number of conductors from 4 to 127. The insulated conductors are twisted; there is a marker pair in each layer. It is allowed digital and color coded marking of the conductors.
Separating layer
Low toxic PVC-compound of low fire hazard.
Screen
For cables of types KVVGЕng(A)- FRLSLTx is made as a helically overlapping superimposed with copper tapes.
Cable armoring
For cables of types KVBbShvng(A)- FRLSLTx is laid helically with two steel, galvanized tapes.
Cable sheath or jacket
Low toxic PVC-compound of low fire hazard.
The cables are designed for fixed connection to electrical devices and equipment, to assemblies of clamps of electrical switch gear with the nominal alternating voltage up to 660V of frequency up to 100 Hz or direct voltage up to 1000V, for group installation with taking into account the volume of combustible load of the cables in buildings, in fire protection systems, fire alarm systems, warning and evacuation in case of fire in buildings, construction and structures with mass stay of people (industrial plants, schools, hospitals, office buildings, railway stations and so on). The screened cables are used when it is necessary to protect the electrical circuits from the influence of external electric fields. The armored cables are used in case of danger of mechanic damage in process of operation, if the cable is not exposed to significant tensile force
The class of fire hazard of the cables according to GOST 31565 П1б.1.2.1.2
Nominal voltage, kV : 0,66
Ambient temperature during cable operation, °С: from -50 to +50
Durably allowable temperature of heating of conductors during operation, °С: +70
Minimum bending radius of the cables at installation, diameters of the cable: armored 10, non-armored 6
The ambient temperature for installation of the cables (without preheat), °С, not below: -15
Smoke generation in the test cell: not more than 50 %
Fire resistance of the cable, minutes, not less than: 180
Service life, years, not less: 30
The cables do not spread combustion at group installation on category: А
Equivalent toxicity index, g/m3 , more than: 120