KPBShvng(A)-FRLS KPvBShvng(A)-FRLS
Specification 16.К71-480-2015
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Conductor
Copper, single-wire, of the 1 class according to GOST 22483-2012, with the cross-section from 1.5 to 6 mm2.
Thermal barrier
Mica tape winding
Insulation
For cables of types KPvBShvng(A)-FRLS – cross-linked, halogen free polymer composition.
For cables of types KPBShvng(A)-FRLS – thermoplastic, cross-linked, halogen free polymer composition.
Core arrangement and twisting
Number of conductors from 4 to 61.
The insulated conductors are twisted in a cable core.
The cables have a digital and color coded marking of the conductors.
Inner sheath
It is made by extrusion with filling with the halogen free polymer compositions.
Cable armoring
It is laid helically with two steel, galvanized tapes.
It is possible to lay the PET-tapes by winding or longitudinally over the armor.
Cable sheath or jacket
PVC-compound of low fire hazard.
The cables are designed for transmission and distribution of electric energy in stationary installations, for installation in cable structures, buildings and underground structures, including flammable and explosive areas, as well as for the power circuits of the equipment that operates in the fire.
The class of fire hazard of the cables according to GOST 31565-2012 П1б.1.2.2.2.
Nominal voltage, kV: 0,66
Ambient temperature during cable operation, °С: from -50 to +50
Resistant with a relative humidity up to 98% at ambient temperature, degree Celsius: +35
Minimum bending radius of the cables, diameters of the cable: 10
Service life, years, not less: 30
Smoke generation in the test cell: not more than 50 %
Test category on the flame retardance : А
Equivalent toxicity index, g/m3 , more than : 40
Fire resistance cables, min, not less: 180
To make an order
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
«*»- required fields