КУГВВнг(А)- LS (KUGVVng(A)-LS) Russian analogue of LiYY Flame Retardant Low Smoke, YSLY, JB-500 КУГВЭВнг(А)- LS (KUGVЕVng(A)-LS) Russian analogue of LiYC5Y Flame Retardant Low Smoke, YCEY КУГВВЭнг(А)- LS (KUGVVЕng(A)-LS) Russian analogue of LiYCY Flame Retardant Low Smoke, YSLCY, JB-500 CY
specifications 16.K71-310-2001
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Current-carrying conductor
Copper, multi-wire of circular form, of the 4 class according to GOST 22483, with the cross-sections from 0.35 and 0.5 mm2.
Insulation
PVC-compound of low fire hazard (color-coded conductors).
Screen
For KUGVЕVng(A)-LS is made in the form of braiding with copper wires over the insulation of each conductor.
Core arrangement and twisting
Insulated conductors (screened and not screened) are twisted in a cable core in the form of concentric layers.
Winding
Lapping with the tapes of PET-E films over the twisted conductors.
Main screen
For cables of type KUGVVЕng(A)-LS is made of alum flex and a contact copper wire.
Over sheath
PVC-compound of low fire hazard.
The cables are designed for fixed installation of control circuits on the nominal alternating voltage up to 380V of frequency up to 50 Hz or direct voltage up to 500V.
The cables are manufactured for general industrial use and nuclear power plants. The cables do not spread combustion at group installation. The cables are designed for use in cable structures and premises, including for objects which use nuclear power, in the systems of NPP of class 3 and 4 according to classification of ОПБ-88/97 (ПНАЭ Г – 01-011).
The climate modification B, categories of location 1 - 5 according to GOST 15150-69.
The class of fire hazard of the cables according to GOST 31565 П1б.8.2.2.2
Nominal voltage, not more than, V | 380 |
Ambient temperature during cable operation, °С | from - 50 to + 50 |
The ambient temperature for laying and installation of the cables (without preheat) is made, °С, not below | -15 |
Minimum bending radius, diameters of the cable | 12 |
Durably allowable temperature of heating of conductors during operation, 0С | 70 |
Service life, years | 30 |
Smoke generation in the test cell | not more than 50% |
Type of cable | Value for rated cross-section of conductors, mm2 | |
0,35 | 0,5 | |
KUGVVng(A)-LS | 7, 14, 24, 37, 61 | - |
KUGVЕVng(A)-LS | 7, 14, 24, 37 | 7, 14, 24, 37 |
KUGVVЕng(A)-LS | 7, 14, 24, 37, 61 | 7, 14, 24, 37, 61 |