КУГВВнг(А)-FRLS (KUGVVng(A)-FRLS)- Russian ana logue of JB-500 Low Smoke FE180/E60
SCOPE AND PURPOSE
The cables are designed for fixed installation of control circuits on the nominal alternating voltage up to 380V of frequency up to 50 Hz or direct voltage up to 500V.
The cables are manufactured for general industrial use and nuclear power plants. The cables do not spread combustion at group installation. The cables are designed for use in cable structures and premises, including for objects which use nuclear power, in the systems of NPP of class 3 and 4 according to classification of ОПБ-88/97 (ПНАЭ Г – 01-011).
The climate modification B, categories of location 1 - 5 according to GOST 15150-69
The class of fire hazard of the cables according to GOST 31565 П1б.1.2.2.2.
STRUCTURE
Current-carrying conductor
Copper, multi-wire of circular form, of the 4 class according to GOST 22483, with the cross-sections from 0.35 and 0.5 mm2.
Thermal barrier
Taped with two mica tapes.
Insulation
PVC-compound of low fire hazard (color-coded or digital-coded conductor).
Core arrangement and twisting
Insulated (screened and not screened) conductors are twisted in a cable core in the form of concentric layers.
Winding
Lapping with PET-E films.
Over sheath
PVC-compound of low fire hazard.
Number of conductors, nominal cross-section (mm2), construction, voltage (kV) | Calculated diameter of cable, mm | Calculated weight of cable, kg/km | |
KUGVVng(A)-FRLS 7х0,35 | 12,1 | 172 | |
KUGVVng(A)-FRLS 14х0,35 | 16,9 | 318 | |
KUGVVng(A)-FRLS 24х0,35 | 22,4 | 531 | |
KUGVVng(A)-FRLS 37х0,35 | 25,9 | 767 | |
KUGVVng(A)-FRLS 61х0,35 | 32,6 | 1199 | |
KUGVVng(A)-FRLS 7х0,5 | - | - | |
KUGVVng(A)-FRLS 14х0,5 | - | - | |
KUGVVng(A)-FRLS 24х0,5 | - | - | |
KUGVVng(A)-FRLS 37х0,5 | - | - | |
KUGVVng(A)-FRLS 61х0,5 | - | - |