КУГВВнг(А)-FRLS (KUGVVng(A)-FRLS)- Russian ana logue of JB-500 Low Smoke FE180/E60 КУГВЭВнг(А)-FRLS (KUGVEVng(A)-FRLS)- Russian analogue of LiYC5Y Flame Retardant Low Smoke FE180/E60, YCEY FE180/E60 КУГВВЭнг(А)-FRLS (KUGVVEng(A)-FRLS)- Russian analogue of JB-500 CY Low Smoke FE180/E60
specifications 16.K71-337-2004
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Current-carrying conductor
Copper, multi-wire of circular form, of the 4 class according to GOST 22483, with the cross-sections from 0.35 and 0.5 mm2.
Thermal barrier
Taped with two mica tapes.
Insulation
PVC-compound of low fire hazard (color-coded or digital-coded conductor).
Screen
For KUGVEVng(A)-FRLS is made in the form of braiding with copper wires over the insulation of each conductor.
Core arrangement and twisting
Insulated (screened and not screened) conductors are twisted in a cable core in the form of concentric layers.
Winding
Lapping with PET-E films.
Screen over twisting
For cables of type KUGVVEng(A)-FRLS braiding with copper or copper galvanized wires.
Over sheath
PVC-compound of low fire hazard.
The cables are designed for fixed installation of control circuits on the nominal alternating voltage up to 380V of frequency up to 50 Hz or direct voltage up to 500V.
The cables are manufactured for general industrial use and nuclear power plants. The cables do not spread combustion at group installation. The cables are designed for use in cable structures and premises, including for objects which use nuclear power, in the systems of NPP of class 3 and 4 according to classification of ОПБ-88/97 (ПНАЭ Г – 01-011).
The climate modification B, categories of location 1 - 5 according to GOST 15150-69
The class of fire hazard of the cables according to GOST 31565 П1б.1.2.2.2.
Nominal voltage, not more than, V | 380 |
Ambient temperature during cable operation, °С | from- 50 to + 60 |
The ambient temperature for laying and installation of the cables (without preheat) is made, °С, not below | -15 |
Minimum bending radius, diameters of the cable | 12 |
Durably allowable temperature of heating of conductors during operation, 0С | 70 |
Service life, years | 30 |
Fire resistance of the cables, min, not less | 180 |
Smoke generation in the test cell | not more than 50% |
Type of cable | Value for rated cross-section of conductors, mm2 | |
0,35 | 0,5 | |
KUGVVng(A)-FRLS | 7, 14, 24, 37, 61 | - |
KUGVEVng(A)-FRLS | 7, 14, 24, 37 | 7, 14, 24, 37 |
KUGVVEng(A)-FRLS | 7, 14, 24, 37, 61 | 7, 14, 24, 37, 61 |