КПСВВГнг(А)-LS (KPSVVGng(A)-LS) - Russian analogue of J-YYH-Bd Flame Retardant Low Smoke

KPSVVGng(A)-LS

Description Add to order

SCOPE AND PURPOSE

The cables are designed for installation of fire and security alarm systems, systems of access control and other management systems, control and communications in the conditions of stationary laying inside of buildings and structures if it is necessary to protect the electric circuits from the influence of external electric fields.

The class of fire hazard of the cables according to GOST 31565 П1б.8.2.2.2

STRUCTURE

Current-carrying conductor

Copper, multi-wire not less than of the 3 class according to GOST 22483, with the cross-sections from 0.2 to 2.5 mm2.

Insulation

PVC-compound of low fire hazard (color-coded conductors).

Core arrangement and twisting

Insulated conductors are twisted in a pair.

Over sheath

PVC-compound of low fire hazard.

Number of pairs in cable, pcs Cross-section, mm2 External dimensions or diameter of cable, mm Calculated weight of 1km of cable, kg/km
KPSVVGng(A)-LS 1 0,2 4,2 21
km
2 4,2х7,2 35
KPSVVGng(A)-LS 1 0,35 4,8 27
km
2 4,7х8,3 47
KPSVVGng(A)-LS 1 0,5 5,1 31
km
2 5,1 х 8,9 55
KPSVVGng(A)-LS 1 0,75 5,8 40
km
2 5,8 х 10,3 71
KPSVVGng(A)-LS 1 1 6,3 47
km
2 6,3 х 11,3 86
KPSVVGng(A)-LS 1 1,5 7 60
km
2 7,0 х 12,7 110
KPSVVGng(A)-LS 1 2,5 8,1 85
km
2 8,1 х 15,0 159