КПСВВнг(А)-LS (KPSVVng(A)-LS) - Russian analogue of J-YYBd Flame Retardant Low Smoke КПСВВГнг(А)-LS (KPSVVGng(A)-LS) - Russian analogue of J-YYH-Bd Flame Retardant Low Smoke КПСВЭВнг(А)-LS (KPSVЕVng(A)-LS) - Russian analogue of J-Y(St)Y-Bd Flame Retardant Low Smoke КПСВЭВГнг(А)-LS (KPSVЕVGng(A)-LS)- Russian analogue of J-Y(St)YH-Bd Flame Retardant Low Smoke КПСВЭЭВнг(А)-LS (KPSVЕEVng(A)-LS) - Russian analogue of J-Y(St)Y(St)-Bd Flame Retardant Low Smoke КПСВЭЭВГнг(А)-LS (KPSVЕEVGng(A)-LS) - Russian analogue of J-Y(St)Y(St)H-Bd Flame Retardant Low Smoke
specifications 16.K121-020-2011
You can pre-order the products. After the receipt of your order a specialist of our company will contact you and offer the best delivery conditions.
Current-carrying conductor
Copper, single-wire of the 1 class or multi-wire not less than of the 3 class according to GOST 22483, with the cross-sections from 0.2 to 2.5 mm2.
Insulation
PVC-compound of low fire hazard (color-coded conductors).
Core arrangement and twisting
Insulated conductors are twisted in a pair.
Screen
Alum polymer tape with a contact conductor of copper, galvanized wire is lapped in the way of winding or longitudinally by overlapping;
-over the twisted pairs of cables KPSVЕVng(A)- LS and KPSVЕVGng(A)-LS;
- over each pair individually in two-pair cables KPSVЕEVng(A)-LS and KPSVЕEVGng(A)-LS
Over sheath
PVC-compound of low fire hazard.
The cables are designed for installation of fire and security alarm systems, systems of access control and other management systems, control and communications in the conditions of stationary laying inside of buildings and structures if it is necessary to protect the electric circuits from the influence of external electric fields.
The class of fire hazard of the cables according to GOST 31565 П1б.8.2.2.2
Nominal voltage, not more than, V | 300 | |
Ambient temperature during cable operation, °С | from – 50 to + 70 | |
The ambient temperature for laying and installation of the cables (without preheat) is made, 0C not below | - 15 | |
Minimum bending radius, diameters of the cable | - with the single wire cores not less | 10 |
-with the multi-wire cores not less | 6 | |
Service life, not less | 15 years | |
Smoke generation in the test cell | not more than 50% |
Table 1
Electric parameters
Name of parameter on frequency 0.8 kHz | Type of cable | Value for rated cross-section of conductors, mm2 | ||||||
0,2 | 0,35 | 0,5 | 0,75 | 1 | 1,5 | 2,5 | ||
Electric capacity, converted on 1 km, nF, not more | КPSVVng(А)-LS, КPSVVGng(А)-LS | 65 | 70 | 75 | 80 | 90 | 100 | 110 |
КPSVEVng(А)-LS, КPSVEVGng(А)-LS, КPSVEEVng(А)-LS, КPSVEEVGng(А)-LS | 70 | 95 | 108 | 116 | 118 | 123 | 138 | |
Attenuation coefficient converted on 1 km of length, dB, not more | КPSVVng(А)-LS, КPSVVGng(А)-LS | 1,8 | 1,45 | 1,33 | 1,06 | 0,93 | 0,68 | 0,58 |
КPSVEVng(А)-LS, КPSVEVGng(А)-LS, КPSVEEVng(А)-LS, КPSVEEVGng(А)-LS | 2,05 | 1,6 | 1,34 | 1,11 | 0,94 | 0,79 | 0,64 |