КПСCнг(А)-FRLS (KPSSng(A)-FRLS) - Russian analogue of JE-2GGSYu...Bd FE240/E60 Keram Low Smoke

KPSSng(A)-FRLS

Description Add to order

SCOPE AND PURPOSE

The cables are designed for single or group fixed laying in fire protection systems, fire alarm systems in warning systems and evacuation management of people during fire, in buildings, constructions and structures ( industrial enterprises, schools, hospitals, office premises, high-rise buildings, subways and nuclear power plants) where requirements for cables and wires to survive in fire conditions exist.

The cables keep working in fire conditions for a period of 240 minutes.

They are operated inside and outside the premises, provided protection from direct affect of solar radiation and precipitation.

The class of fire hazard of the cables according to GOST 31565 П1б.1.2.2.2.

STRUCTURE

Current-carrying conductor

Copper, single-wire of the 1 class according to GOST 22483, with the cross-sections from 0.2; 0.35; 0.5; 0.75; 1; 1.5; 2.5mm2.

Insulation

Silicon organic rubber (color-coded conductors).

Core arrangement and twisting

Insulated conductors are twisted in pairs.

Thermal barrier

Taped with one mica tape over each twisted pair.

Twisted pairs wrapped with a mica tape are situated in parallel in the cables with two pairs.

Over sheath

PVC-compound of low fire hazard.

Number of conductors, nominal cross-section (mm2), construction, voltage (kV) Calculated diameter of cable, mm Calculated weight of cable, kg/km
KPSSng(A)-FRLS 1х2х0,2 4,8 25
km
KPSSng(A)-FRLS 1х2х0,35 5,4 32
km
KPSSng(A)-FRLS 1х2х0,5 5,8 37
km
KPSSng(A)-FRLS 1х2х0,75 6,2 44
km
KPSSng(A)-FRLS 1х2х1,0 6,7 52
km
KPSSng(A)-FRLS 1х2х1,5 7,3 66
km
KPSSng(A)-FRLS 1х2х2,5 8,3 90
km
KPSSng(A)-FRLS 2х2х0,2 4,8х8,4 44
km
KPSSng(A)-FRLS 2х2х0,35 5,4х9,5 56
km
KPSSng(A)-FRLS 2х2х0,5 5,8х10,4 66
km
KPSSng(A)-FRLS 2х2х0,75 6,2х11,0 80
km
KPSSng(A)-FRLS 2х2х1,0 6,7х12,0 96
km
KPSSng(A)-FRLS 2х2х1,5 7,3х13,4 122
km
KPSSng(A)-FRLS 2х2х2,5 8,3х15,4 169
km